UL cautions, warnings, and instructions

Wiring warnings for electrical practices and wire sizes
The Cautions, Warnings, and Instructions in this section summarize
the procedures necessary to ensure an inverter installation complies
with Underwriters Laboratories® guidelines.
en
Warning!
Use 60/75°C Cu wire only or equivalent.
en
Warning!
Open type equipment.
en
Warning!
Suitable for use on a circuit capable of
delivering not more than 5,000 rms
symmetrical amperes:
• 240 V maximum for DM1-32 models
• 500 V maximum for DM1-34 models
• 600 V maximum for DM1-35 models
Circuit breaker and fuse sizes
The adjustable frequency drive's connections to input power must
include UL listed inverse time circuit breakers with 600 V rating, or
UL listed fuses.
Technical support contact information
Americas
Website
www.eaton.com/drives
Email
VFDaftermarketEG@eaton.com
Phone
1-877-386-2273 (8:00 a.m. to 6:00 p.m.
Eastern Time U. S. [UTC–5])
800-543-7038 (6:00 p.m. to 8:00 a.m.
Eastern Time U.S. [UTC–5])
TRCDrivesTechSupport@eaton.com
Wire connectors
Cable
Cable
Motor overload protection
DM1 adjustable frequency drives provide solid-state motor overload
protection, which depends on the proper setting of the following
parameter: P5.1.2 "current limit. "
"The setting range is (0.2 * rated current) to (2 * rated current).
EMEA
APAC
www.eaton.com/AfterSales
www.eaton.com.cn/electrical
AfterSalesEGBonn@eaton.com
CustomerServicePDCNA@eaton.com
+49 (0) 180 5 223822
800 9881203
Instruction Leaflet
en
Warning!
Field wiring connections must be made by a UL
listed and CSA certified ring lug terminal connec-
tor sized for the wire gauge being used. The
connector must be fixed using the crimping tool
specified by the connector manufacturer.
Cable
Cable support
en
Warning!
When two or more motors are connected
to the inverter, they cannot be protected by
the electronic overload protection. Install an
external thermal relay on each motor.
EATON www.eaton.com
PUB53675
Effective December 2021
PE