PowerXL DM1 and DM1 Pro series VFD
Table 4. Connection sizes and torques.
Input voltage
Frame
Drive
size
catalog
number
380 Vac to 480 Vac
FR1
DM1-341D5... 1.5
50/60 Hz
DM1-342D2... 2.2
3 phase
DM1-344D3... 4.3
DM1-345D6... 5.6
FR2
DM1-347D6... 7.6
DM1-34012... 12
DM1-34016... 16
FR3
DM1-34023..
FR4
DM1-34031... 31
DM1-34038... 38
525 Vac to 600 Vac
FR2
DM1-351D7... 1.7
50/60 Hz
DM1-352D7... 2.7
3 phase
DM1-354D5... 4.5
DM1-357D5... 7.5
DM1-35010... 10
FR3
DM1-35013... 13.5
FR4
DM1-35018... 18
DM1-35022... 22
Notes:
Strip the motor and power cables as shown above.
Both UL
and IEC tools may be used.
®
Applies to strained wire, solid wire, or ferrule installations.
(Continued).
Output rating
Size and torque
CT/IH
VT/IL
Power
Power wire
current
current
wire size
torque
amps
amps
AWG
in.-lb (N·m)
(mm2)
2.2
14 (2.5)
4.4 (0.5)
4.3
14 (2.5)
4.4 (0.5)
5.6
14 (2.5)
4.4 (0.5)
7.6
14 (2.5)
4.4 (0.5)
12
12 (4)
10.5 (1.2)
16
10 (6)
10.5 (1.2)
23
8 (10)
10.5 (1.2)
23
31
8 (10)
10.5 (1.2)
38
6 (16)
33 (3.73)
46
4 (25)
33 (3.73)
2.7
12 (4)
10.5 (1.2)
4.5
12 (4)
10.5 (1.2)
7.5
12 (4)
10.5 (1.2)
10
12 (4)
10.5 (1.2)
13.5
12 (4)
10.5 (1.2)
18
8 (10)
10.5 (1.2)
22
6 (16)
33 (3.73)
27
4 (25)
33 (3.73)
Instruction Leaflet
Ground
Ground
Control
wire size
wire
wire size
AWG
torque
AWG (mm2)
(mm2)
in.-lb (N·m)
14 (2.5)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
14 (2.5)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
14 (2.5)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
10 (2.5)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
10 (4)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
10 (6)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
10 (10)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
8 (10)
14.2 (1.6)
28-16 (0.5-1.5) 1.73 (0.2)
8 (16)
14.2 (1.6)
28-16 (0.5-1.5) 1.73 (0.2)
8 (16)
14.2 (1.6)
28-16 (0.5-1.5) 1.73 (0.2)
10 (4)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
10 (4)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
10 (4)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
10 (4)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
10 (4)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
8 (10)
14.2 (1.6)
28-16 (0.5-1.5) 1.73 (0.2)
8 (16)
14.2 (1.6)
28-16 (0.5-1.5) 1.73 (0.2)
8 (16)
14.2 (1.6)
28-16 (0.5-1.5) 1.73 (0.2)
EATON www.eaton.com
PUB53675
Effective December 2021
Control
RO
wire torque
in.-lb (N·m)
AI/DI
4.5 (0.5)
4.5 (0.5)
4.5 (0.5)
4.5 (0.5)
4.5 (0.5)
4.5 (0.5)
4.5 (0.5)
4.5 (0.5)
4.5 (0.5)
4.5 (0.5)
4.5 (0.5)
4.5 (0.5)
4.5 (0.5)
4.5 (0.5)
4.5 (0.5)
4.5 (0.5)
4.5 (0.5)
4.5 (0.5)
15