PowerXL DM1 and DM1 Pro series VFD
Table 7. I/O connection (continued).
DM1 PRO
External wiring Terminal Short name
1
DI1
1
2
DI2
2
3
DI3
3
4
DI4
4
5
CMA
5
6
6
A
7
7
B
8
AI1+
8
9
AI1-
9
10
GND
10
11
AO1+
11
12
12
GND
13
13
10 V
14
14
24 V
15
15
STO_com
16
16
STO2
17
17
STO1
18
18
R1NO
19
19
R1CM
20
R1NC
20
21
R2NO
21
22
R2CM
22
Notes:
The above wiring demonstrates a SINK configuration. The SW2 position 1 is set to ON. If a SOURCE configuration is desired, wire 24 V to CMA and close the inputs to ground.
When using the +10 V for AI1, SW2 position 2 set to ON.
AI1+ support 10 K potentiometer.
Name
Default setting
Digital input 1
Run forward
Digital input 2
Run reverse
Digital input 3
External fault
Digital input 4
Fault reset
DI1 to DI4 common
Grounded
RS-485 signal A
—
RS-485 signal B
—
Analog input 1
0 - 10 V
Analog input 1 ground
—
I/O signal ground
—
Analog output 1
Output frequency
I/O signal ground
—
10 Vdc reference output
10.3 Vdc +/- 3%
24 Vdc control output
24 Vdc In/Out
Safe torque common
—
Safe torque Off 2
—
Safe torque Off 1
—
Relay 1 normally open
Run
Relay 1 common
Relay 1 normally closed
Relay 2 normally open
Fault
Relay 2 common
Instruction Leaflet
Description
Starts the motor in the forward direction.
Start the motor in the reverse direction.
Triggers a fault in the drive.
Resets active faults in the drive.
Allows for sourced input.
Fieldbus communication (Modbus RTU, BACNet).
Fieldbus communication (Modbus RTU, BACNet).
Voltage speed reference (programmable to 4 mA to 20 mA).
Analog input 1 common (ground).
I/O ground for reference and control.
Shows output frequency to motor 0 - 60 Hz (4 mA to 20 mA).
I/O ground for reference and control.
10 Vdc reference voltage.
Control voltage input/output (100 mA max.).
Safe torque Off common.
Safe torque Off 2 input.
Safe torque Off 1 input.
Changes state when the drive is in the run state.
Changes state when the drive is in the fault state.
EATON www.eaton.com
PUB53675
Effective December 2021
21