Operational Check - Assa Abloy SARGENT IN120 Wi-Fi Series Installation Instructions Manual

Exit device
Table of Contents

Advertisement

IN120 / IN220 Exit Device

Operational Check

11
IMPORTANT: Be sure to test functions prior to closing door.
In all cases, perform the following checks:
1. Ensure that inside exit bar retracts latch.
• To test cylinder, the following checks apply:
Insert key into cylinder and rotate:
a. There should be no friction against lock case, wire
harness, or any other obstructions. If friction or
binding occurs, readjust cylinder and wiring harness
to eliminate issues.
b. The key should unlock the outside lever and
the lever should rotate freely.
• For units without a keypad, add card using LCT
software* and then test.
• For units with a keypad, add pin and card using
LCT software* and then test.
2. LED signaling:
• After using a valid credential a green flash followed
by motor unlock indicates normal operation (lock
unlocks)
• After using a valid credential a green flash followed
by 4 beeps and 4 fast purple flashes – indicates
low power. Check the input voltage.
• If the input voltage is low, disconnect lock from
power source and check power source voltage.
If power source voltage is correct, inspect lock
wiring for a possible short.
If the lock loses power, it will flash rapid blue for approximately one minute.
Lock will default to programmed fail safe or fail secure.
After that, the lock will no longer be functional.
When you have completed the tests, close the door, ensuring latchbolt fully
extends into strike plate without binding.
*
Twenty (20) seconds after lock initialization
1-800-810-WIRE • www.sargentlock.com • A8185D
(single beep with lock motor actuation).
31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sargent n220 poe series

Table of Contents