During floor drying, all the buttons except OK are invalid.
When the heat pump malfunctions, the floor drying mode
will turn off when the backup heater and additional
heating source is unavailable. If you want to turn off floor
drying up, please press OK. The following page will be
displayed:
12.3 FLOOR DRYING UP
The unit will operate floor drying up
on 09:00 01-08-2018.
OK
CONFIRM
Use
to scroll the cursor to YES and press OK. Floor
drying will turn off.
The target outlet water temperature during floor drying up
described in the picture below:
T1S
T_DRYPEAK
t_DRYUP
t_HIGHPEAK
9.5.13 AUTO RESTART
The AUTO RESTART function is used to select whether
the unit reapplies the user interface settings at the time
when power returns after a power supply failure.
Go to MENU> FOR SERVICEMAN>13.AUTO RESTART
13 AUTO RESTART
13.1 COOL/HEAT MODE
13.2 DHW MODE
ADJUST
t
t_DRYD
YES
NON
57
The AUTO RESTART function reapplies the user
interface settings at the time of the power supply failure. If
this function is disabled, when power returns after a
power supply failure, the unit won't auto restart.
9.5.14 POWER INPUT LIMITATION
How to set the POWER INPUT LIMITATION
Go to MENU> FOR SERVICEMAN>
14.POWER INPUT LIMITATION
14 POWER INPUT LIMITATION
14.1 POWER LIMITATION
ADJUST
9.5.15 INPUT DEFINE
How to set the INPUT DEFINE
Go to MENU> FOR SERVICEMAN> 15.INPUT DEFINE
15 INPUT DEFINE
15.1 ON/OFF(M1M2)
15.2 SMART GRID
15.3 T1b(Tw2)
15.4 Tbt1
15.5 Tbt2
ADJUST
15 INPUT DEFINE
15.6 Ta
15.7 SOLAR INPUT
15.8 F-PIPE LENGTH
15.9 dTbt2
15.10 RT/Ta_PCB
ADJUST
0
REMOTE
NON
NON
NON
NON
HMI
NON
<10m
12°C
NON