9.5.5 TEMP. TYPE SETTING
About TEMP. TYPE SETTING
The TEMP. TYPE SETTING is used for selecting whether
the water flow temperature or room temperature is used to
control the ON/OFF of the heat pump.
When ROOM TEMP. is enabled, the target water flow
temperature will be calculated from climate-related curves .
How to enter the TEMP. TYPE SETTING
Go to MENU> FOR SERVICEMAN> 5.TEMP. TYPE
SETTING. Press OK. The following page will be
displayed:
5 TEMP. TYPE SETTING
5.1 WATER FLOW TEMP.
5.2 ROOM TEMP.
5.3 DOUBLE ZONE
ADJUST
If you only set WATER FLOW TEMP. to YES, or only set
ROOM TEMP. to YES, The following pages will be
displayed.
only WATER FLOW TEMP. YES
only ROOM TEMP. YES
If you set WATER FLOW TEMP. and ROOM TEMP. to
YES, meanwhile set DOUBLE ZONE to NON or YES, the
following pages will be displayed.
YES
NON
NON
52
Homepage (zone 1)
In this case, the setting value of zone 1 is T1S,the setting
value of zone 2 is T1S2(The corresponding TIS2 is
calculated according to the climate related curves.)
If you set DOUBLE ZONE to YES and set ROOM TEMP.
to NON, meanwhile set WATER FLOW TEMP. to YES or
NON,the following pages will be displayed.
Homepage (zone 1)
2
Addition page (zone 2)
(Double zone is effective)
2
Addition page (zone 2)