Disabling a zone

Zones can be disabled using the front panel. Disabling a zone
disables all of the devices that are in that zone. A disabled zone does
not report an off-normal condition to the panel while it is disabled.
When you disable a zone:
The common Disable LED turns on
On a zone/device system, the LCD displays disabled messages
for the zone and all of the devices in the zone
On a zone only system, the LCD displays a disabled message for
the zone
The common Trouble LED flashes and the panel goes into a
trouble state
The common trouble relay changes state
The disabled points and active points counters on the LCD
display increment
If you are using an LED display expander, the zone LEDs blink
for the disabled zone
Resetting the panel has no effect on a disabled zone, but removing
all power from the panel clears the disable and enables the zone.
Note:
If the zone you are disabling contains devices that are active,
a warning message is displayed.
To disable a zone:
1.
Press the Menu button.
2.
Choose Control.
3.
Enter your password (the minimum of a level one password is
required).
4.
Choose Enable/Disable.
5.
Choose Zone.
6.
Select the zone that you want to disable.
7.
Press Enter.
8.
If devices in the zone are active, acknowledge the warning
message by selecting Continue to disable the zone or Cancel to
exit.
The zone is disabled.
9.
Press Cancel to return to the previous menu.
36
Reports
Test
Control
Program
Enter Password
0000
Control
Enable/Disable
Activate/Restore
Enable/Disable
Device
Zone
Panel Event
EST iO64 and iO500 Technical Reference Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Est io500

Table of Contents