CMS device programming

CMS devices are your central monitoring station devices, which
include the dialer and network. These are the devices that transmit
system events to a central monitoring station's receiver.

CMS device programming

Dialer
Network
Swinger shutdown
EST iO64 and iO500 Technical Reference Manual
See "Dialer programming."
See "Network programming."
Set swinger shutdown to Off or 1 to 255 repetitions. When finished, press Enter to save. Note:
Off is the only acceptable setting for UL/ULC installations. Refer to "UL 864 programming
requirements" for details.
This automatically inhibits the number of consecutive times a single trouble event is
transmitted over a 24-hour period before it is no longer sent. Some trouble events are not
affected when swinger shutdown is set. They are:
- Loop 1 initializing
- Loop 1 uncfgrd alarm
- Loop 1 map mismatch
- Loop 1 over limits
- Loop 1 device 000
- Loop 1 mapping
- Loop 1 map fault
- Loop 2 initializing
- Loop 2 map mismatch
- Loop 2 over limits
- Loop 2 device 000
- Loop 2 mapping
- Loop 2 map fault
- System startup
- Reset
- Reset/Sil inhibit
- Panel silence
- Program mode
- Signal silence
- Date
- Drill
- Walk test
- Test fire
- Time
- Clear history
- Common alarm
- Common disable
- Common monitor
- Common supervisory
- Common trouble
- Battery charger
- Battery low
- Battery missing
- Local AC power
- System wide AC power
- Self test fault
- Dialer dsbl/rem disc
- Dialer normal test
- Dialer abnormal test
- Dialer configuration
Chapter 3: Programming
137