15. Set trouble event notification.
Printer: Yes or No. Specifies if event information is printed
Coder: 4-digit coded output, which is played in response to
alarm conditions (00-00-00-00 to 99-99-99-99)
Dialer:
Acct 1 & 2: Event information is sent to both dialer accounts
Acct 1: Event information is sent to dialer account one
Acct 2: Event information is sent to dialer account two
None: Event information is not sent to the dialer
NET: Yes or No. Specifies if event information is sent to the
connected network
CID: Contact ID event code (000 to 999)
16. When finished, choose Save.
17. Continue programming your system or press Menu to exit menu
mode.
EST iO64 and iO500 Technical Reference Manual
Chapter 3: Programming
Common Trouble
Correlation Groups
Event Notification
Correlation Groups
Group 01
No<>
Group 02
No<>
Group 03
No<>
Correlation Groups
Group 31
No<>
Group 32
No<>
Save
Common Trouble
Correlation Groups
Event Notification
Trouble
Printer
Yes<>
Code
10-10-10-10
Dialer
Account 1&2
Trouble
NET
Yes
CID
110
Save