Chapter 5: Diagnostics, maintenance, and testing
If auxiliary power is resettable, the auxiliary power is interrupted
while the zone is reset.
Input zones programmed as waterflow with retard require 10 to
15 seconds of activation to initiate the test signals.
Devices programmed as alarm verify and not in test mode go
directly into alarm if activated (the alarm verification process is
bypassed).
Once a device is tested, restore the device. For example, if you
are testing a pull station, reset the pull station before testing the
next device.
The panel terminates walk test if any of the following occur:
There are 30 minutes of inactivity for the zone or device being
tested.
Walk test is stopped by the user.
To start a walk test:
1.
Press the Menu button.
2.
Choose Test.
3.
Choose Walk Test Silent or Walk Test Audible.
4.
Enter your password (the minimum of a level one password is
required).
5.
Choose either All Devices or Zone.
6.
If you chose Zone, enter the zone ID for the zone you are going
to conduct the walk test.
7.
Choose Start.
8.
Conduct your walk test.
9.
Press Cancel to return to the previous menu.
— or —
Press the Menu button to exit menu mode.
196
Reports
Test
Control
Program
Test
Walk Test Silent
Walk Test Audible
Test Fire
Enter Password
0000
Walk Test Sil/Aud
All Devices
Zone
Zone
Number
Zone 01
Start
End
EST iO64 and iO500 Technical Reference Manual