Appendix B: Worksheets
Table 5: Longest allowable circuit path with 11 to 15 SIGA-UMs or SIGA-MABs configured for 2-wire smoke detectors
Number of
Number of
detectors
modules (1
or 2 channel)
1 to 25
0
26 to 50
0
51 to 75
0
76 to 100
0
101 to 125
0
0
1 to 25
1 to 25
1 to 25
26 to 50
1 to 25
51 to 75
1 to 25
76 to 100
1 to 25
101 to 125
1 to 25
0
26 to 50
1 to 25
26 to 50
26 to 50
26 to 50
51 to 75
26 to 50
76 to 100
26 to 50
101 to 125
26 to 50
0
51 to 75
1 to 25
51 to 75
26 to 50
51 to 75
51 to 75
51 to 75
76 to 100
51 to 75
101 to 125
51 to 75
0
76 to 95
1 to 25
76 to 95
26 to 50
76 to 95
51 to 75
76 to 95
76 to 100
76 to 95
101 to 125
76 to 95
222
Maximum allowable wire distance using nontwisted, nonshielded and
twisted, nonshielded wire pairs (evenly distributed)
18 AWG
ft.
m
1817
554
1070
326
321
98
0
0
0
0
1490
454
745
227
0
0
0
0
0
0
0
0
421
128
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
16 AWG
ft.
m
2887
880
1699
518
510
156
0
0
0
0
2367
721
1184
361
0
0
0
0
0
0
0
0
668
204
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
EST iO64 and iO500 Technical Reference Manual
14 AWG
ft.
m
4592
1400
2703
824
811
247
0
0
0
0
3764
1147
1883
574
0
0
0
0
0
0
0
0
1063
324
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0