GE EST iO64 Technical Reference Manual page 275

Table of Contents

Advertisement

Model name
Device type
CRR
Relay Non-Silenceable
CRR
Relay Silence
MCR
Relay Non-Silenceable
MCR
Relay Silence
MCRR
Relay Non-Silenceable
MCRR
Relay Silence
CR2
Relay Non-Silenceable
CR2
Relay Silence
UM
Smoke
UM
Heat
UM
Pull Station
UM
Water Flow
UM
Supervisory Latching
UM
Supervisory Nonlatching
UM
Monitor
UM
Remote Reset
UM
Remote Drill
UM
Remote Signal Silence
UM
Remote AC Fail
UM
Alarm
UM
2-Wire Alarm
UM
2-Wire Alarm Verify
UM
2-Wire Alarm Class A
UM
2-Wire Alarm Verify Class A
UM
Alarm Class A
UM
Pull Station Class A
UM
Heat Class A
UM
Smoke Class A
UM
Water Flow Class A
UM
Supervisory Latching Class A
UM
Supervisory Nonlatching Class A
UM
Monitor Class A
UM
Remote AC Fail Class A
UM
None
UM
Relay Non-Silenceable
UM
Relay Silence
UM
Supervised
EST iO64 and iO500 Technical Reference Manual
Appendix E: Device types to personality codes correlation
Personality code
(8) Signal - dry contact output
(8) Signal - dry contact output
(8) Signal - dry contact output
(8) Signal - dry contact output
(8) Signal - dry contact output
(8) Signal - dry contact output
(8) Signal - dry contact output
(8) Signal - dry contact output
(1) Alarm - NO latching (Class B)
(1) Alarm - NO latching (Class B)
(1) Alarm - NO latching (Class B)
(2) Alarm - NO delayed latching (Class B)
(4) Active - NO latching (Class B)
(3) Active - NO nonlatching (Class B)
(3) Active - NO nonlatching (Class B)
(3) Active - NO nonlatching (Class B)
(3) Active - NO nonlatching (Class B)
(3) Active - NO nonlatching (Class B)
(3) Active - NO nonlatching (Class B)
(1) Alarm - NO latching (Class B)
(13) Alarm - two-wire smoke unverified (Class B)
(14) Alarm - two-wire smoke verified (Class B)
(20) Alarm - two-wire smoke unverified (Class A)
(21) Alarm - two-wire smoke verified (Class A)
(9) Alarm - NO latching (Class A)
(9) Alarm - NO latching (Class A)
(9) Alarm - NO latching (Class A)
(9) Alarm - NO latching (Class A)
(10) Alarm - NO delayed latching (Class A)
(12) Active - NO latching (Class A)
(11) Active - NO nonlatching (Class A)
(11) Active - NO nonlatching (Class A)
(11) Active - NO nonlatching (Class A)
(0) No Personality
(8) Signal - dry contact output
(8) Signal - dry contact output
(16) Signal - supervised output (Class B)