Chapter 3: Programming
Line 1 and 2
Cut duration/supervision:
Tone wait seconds
Call disconnect seconds
Test frequency days
Test time
Rings to answer
Ring type
Callback
Callback number
To program the dialer:
1.
Access the panel configuration options menu. See "Panel
configuration options."
2.
Choose CMS Device.
3.
Choose Dialer.
4.
Program the dialer using the "Dialer programming options"
table above. For dialer default settings, see "Factory default
settings."
5.
When you're finished programming each option, choose Save.
6.
Continue programming your system or press Menu to exit menu
mode.
140
Event: Only the event type (alarm, supervisory, trouble, etc.) is
reported/transmitted, no device or zone information. Note: This setting uses the
CMS event notification settings for reporting events. Make sure your event
notification settings are correct. Refer to "CMS device programming" for more
information.
Program line 1 options, and then program line 2 options. When finished
programming each line, choose Save.
Dialing:
Select Tone or Pulse dialing.
Set the cut duration/supervision to Off or 10 to 120 seconds. Specifies the length of
time a phone line trouble is detected before reporting the trouble.
Set tone wait to Off or 1 to 30 seconds. Specifies how long the dialer waits to get a
dial tone.
Set call disconnect to Off or 1 to 45 seconds. Specifies the length of time the dialer
seizes the line (to disconnect parallel devices) before attempting to dial out.
Set test frequency to Off or 1 to 45 days. Specifies how often the dialer performs a
test call. Note: The "off" setting is not acceptable for UL/ULC installations. Refer to
"UL 864 programming requirements" for details.
Set the test time to the desired time of day for running the test.
Set rings to answer to Off or 1 to 15 rings. Specifies how many rings before the dialer
answers incoming calls.
Set ring type to Any or Normal. Specifies the type of ring expected when an incoming
call is received.
Select Enabled or Disabled.
Enter the callback phone number (up to 20 digits). This specifies the phone number
that is used for call back.
Panel Configuration
Ann. Class
Annunciator
CMS Device
CMS Device
Dialer
Network
Swngr Shtdn Rp.200<>
Dialer
Type
Single Line>
Account 1
Account 2
CMS Device
Swngr Shtdn Rp.200<>
Event Notification
Save