Silencing notification appliances

Pressing the Signal Silence button turns off all audible appliances.
Visible appliances or NAC circuits may or may not turn off,
depending on panel programming.
When you silence the signals:
The Signal Silence LED lights, indicating that the notification
appliances are off
If Genesis horn/strobe or horn-only devices are used on NACs
programmed for Genesis operation, Signal Silence silences the
horns and strobes based on system programming
Note:
NACs activated by devices programmed as waterflow cannot
be silenced until the activated devices are restored to normal via a
panel reset. After the waterflow device events restore, the Signal
Silence button or the auto signal silence timer can silence the NACs
if there are other events causing the NACs to activate.
To silence notification appliances:
1.
Press the Signal Silence button.
Signal Silence button
00:00:00
01/01/07
,
When the auto signal silence timer is programmed
When an event activates the notification appliances, the 5- to 30-
minute auto signal silence timer is activated. The time duration is set
in system programming. The notification appliances are activated
EST iO64 and iO500 Technical Reference Manual
Chapter 1: System operation
WARNING: The notification
appliances should not be
silenced until the building is
fully evacuated and the cause
of the alarm has been
determined.