Alarm Settings - Airstream Cumberland EXPERT LA User Manual

Temperature controller
Table of Contents

Advertisement

EXPERT LA

11.3 Alarm Settings

Select:
Main menu
Start/Stop*
Alarms
*
A password may be required to access this menu (sec. 4.2).
Temperature
Clean Mode
Low Alarm
High Alarm
Critical Alarm
Water 1 Spill Limit
Water 2 Spill Limit
Static Pressure Alarm
Low Alarm
High Alarm
Delay
Feed Monitoring?
Feeder 1 Max Time
Feeder 2 Max Time
Activate the alarm relay with
Water Spill
Lo Temperature
Hi Temperature
Lo Stat. Pres.
Hi Stat. Pres.
Defect. sensors
Comm. Error
Whisker Defect
Use
Set the following alarm limits:
Refer to the previous page to get further informa-
tion about these parameters).
Temperature Alarms
Clean mode: Set the temperature below
which a temperature alarm is set off in
clean mode.
Accessible if the Clean mode's low temp. alarm
is enabled (see sec. 4.10).
Lo/Hi alarm: Set the room temperature
below and above which a temperature alarm
is set off.
Main menu
Start/Stop
Alarms
Alarm Settings
Alarms
32.0 °F
60.0 °F
90.0 °F
100.0 °F
100 Lit
100 Lit
.010 "WC
.100 .WC
300 sec
Yes
5 min
None min
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
to navigate
Critical temperature: Set the absolute tem-
perature above which an alarm is set off.
Accessible if an outside temperature probe is
enabled (section 4.7.1).
Water spill limit
Specify the maximum amount of water that can
be consumed by each water meter per 15 min-
utes (0-10,000 gal or liters/15 min).
Accessible if a water meter is enabled (sec. 4.7.1)
Static pressure limit
Accessible if a static pressure probe is enabled
(section 4.7.1).
Low / High alarm: Set the pressure
levels below and above which an alarm
is set off.
Delay: The high or low pressure condi-
tion must be maintained on this period
of time before the controller sets off
the alarm. Set the static pressure alarm
delay to the desired value (in seconds).
Feeder monitoring
Select "Yes" if you want the controller to
monitor the run time of feeding inputs. If
this alarm condition is enabled, set the maxi-
mum run time of each feeder (in minutes).
Refer to section 4.8 to assign the relay that
must open in case of a run time alarm.
Accessible if feeders are enabled (section 4.5).
Activate the alarm relay:
Select "Yes" if you want the controller to
activate the alarm relay when the following
alarm conditions occur:
- Lo / Hi Temperature;
- Lo / Hi Static pressure;
- Water spill;
- Defective sensors: temperature
humidity, static pressure;
- Defective whisker switch.
[Alarm conditions that are activating the alarm
relay are common to all programs].
EXPERT LA rev.00
71