Airstream TC4-2N6F User Manual

Airstream TC4-2N6F User Manual

Combined ventilation control

Advertisement

Quick Links

TC4-2N6F

Advertisement

Table of Contents
loading

Summary of Contents for Airstream TC4-2N6F

  • Page 1 TC4-2N6F...
  • Page 2 Enter the serial number located on the side of the controller below for future reference. Model number: TC4-2N6F Serial number: Every effort has been made to ensure that this manual is complete, accurate and up-to-date. The information contained in it is however subject to change without notice due to further developments.
  • Page 3: Table Of Contents

    Stage 1 Fans ................... 24 Stage 2 Fans ................... 32 Stage 3 and 5 Fans ................34 Curtains .................... 36 Mist ....................39 Heaters ..................... 41 Locking the Parameters ..............42 TROUBLESHOOTING GUIDE ............. 43 TECHNICAL SPECIFICATIONS ............47 TC4-2N6F.rev.07...
  • Page 4: Features

    TC4-2N6F is an electronic device used for environmental control in livestock buildings. It allows the user to maintain a specified target temperature by controlling the operation of ventilation and heating equipment. Two stages of variable speed fans, two stages of constant speed fans, as well as curtains, foggers and heaters can be connected to the controller.
  • Page 5 COMPUTER CONTROL When used with a communication module, the controller communi- cates with a computer. This makes possible the centralization of in- formation management and a more diversified control strategy. TC4-2N6F.rev.07...
  • Page 6: Precautions

    To avoid exposing the controller to harmful gases or exces- sive humidity, it is preferable to install it in a corridor. The room temperature where the controller is located MUST ALWAYS REMAIN BETWEEN 32° AND 104°F (0° AND 40°C). DO NOT SPRAY WATER ON THE CONTROLLER TC4-2N6F.rev.07...
  • Page 7: Location Of The Controls

    TC4-2N6F.rev.07...
  • Page 8 Turns on when a probe is defective. Locked parameter pilot light Turns on when the parameters are locked. Push-button Used to access the various adjustments. Parameter selection knob Used to select a parameter. Adjustment knob Used to adjust the value of a selected parameter. TC4-2N6F.rev.07...
  • Page 9 Used to set the operating modes as described in the table below. SWITCH DESCRIPTION OPERATING MODE POSITION Locked parameters Parameters Unlocked parameters ° Celsius Temperature units ° Fahrenheit 1°F (0.6°C) Heater differential 2 °F (1.1°C) 1°F (0.6°C) Heater offset 2 °F (1.1°C) TC4-2N6F.rev.07...
  • Page 10: Installation

    It may be necessary to install a trans- former on the heating stage in order to supply the correct voltage to the Inside of the enclosure heater. TC4-2N6F.rev.07...
  • Page 11 (6.22 and 6.60 mm) to ensure the cable entry is liquid-tight (the cable dimension should not be under 18 AWG). It is preferable to weld the cable joint to ensure a proper contact between the two cables. Do not ground the shielding. TC4-2N6F.rev.07...
  • Page 12 Press the push-button. If the probe connected to terminal # 2 is not defective, the letter "b" is displayed, alternating with the temperature mea- sured by probe B. Otherwise, the letter "b" is displayed, alternating with the letter "P". TC4-2N6F.rev.07...
  • Page 13 10 seconds without changing the position of the adjustment knob. To Select a Motor Curve for Stage 2 Repeat the steps described above, this time setting the parameter selection knob to DIFFERENTIAL - STAGE 2. TC4-2N6F.rev.07...
  • Page 14: Operation Diagram

    TC4-2N6F.rev.07...
  • Page 15: Using The Controller

    Time on of 1 minute 0 to 60 minutes, by increments MIST Time off of 1 minute Differential 0.5° to 20.0°F (0.3° to 11.1°C) 1.0° or 2.0°F (0.6° or 1.1°C) Differential HEATERS Offset 1.0° or 2.0°F (0.6° or 1.1°C) TC4-2N6F.rev.07...
  • Page 16: Factory Settings

    30 seconds Time off CURTAINS 90 seconds Dead band 2.0°F (1.1°C) Differential 3 and 5 STAGE 3&5 FANS 2.0°F (1.1°C) Time on 1 minute MIST Time off 15 minutes Differential 10°F (5.6°C) Differential 2.0°F (1.1°C) HEATERS Offset 2.0°F (1.1°C) TC4-2N6F.rev.07...
  • Page 17: The Meaning Of A Flashing Display

    Set switch # 2 to the desired position: ON to display temperatures in degrees Celsius. OFF to display temperatures in degrees Fahrenheit. FACTORY SETTING: When the controller is shipped from the factory, switch # 2 is set to OFF (temperatures are displayed in degrees Fahrenheit). TC4-2N6F.rev.07...
  • Page 18: Room Temperature

    Press the push-button. The letter "A" and the zone A tempera- ture alternately appear on the display. Press the push-button once again. The letter "B" and the zone B temperature alternately appear on the display. Press the push-button once again. The room temperature again appears on the display. TC4-2N6F.rev.07...
  • Page 19: Minimum And Maximum Temperature Recall

    TO RESET THE MINIMUM AND MAXIMUM TEMPERATURES Set the parameter selection knob to ROOM. The room temperature appears on the display. TC4-2N6F.rev.07...
  • Page 20: Room Set Point / Temperature Curve

    The controller continues to operate according to the last room set point until you activate the temperature curve once again or specify a new room set point. You can also deactivate the temperature curve before the last point is reached. TC4-2N6F.rev.07...
  • Page 21 Be sure the temperature curve is deactivated (read the instructions above). Set the parameter selection knob to SET POINT/ T°CURVE. The current room set point appears flashing on the display. Using the adjustment knob, adjust the set point to the desired value. TC4-2N6F.rev.07...
  • Page 22 Using the adjustment knob, adjust the day number to the desired value. Press the push-button once again. The current room set point for this day number appears flashing on the display. Using the adjustment knob, adjust the room set point to the desired value. TC4-2N6F.rev.07...
  • Page 23 Set the parameter selection knob to SET POINT / T CURVE. The current temperature set point appears on the display. Press the push-button. The current day number is displayed. Use the adjustment knob to set the day number to the desired value. TC4-2N6F.rev.07...
  • Page 24: Outside Temperature

    If the outside set point is deactivated, the curtains operate according to the curtain timer settings with no outside temperature compensation. refer to "Curtains", page 35) TC4-2N6F.rev.07...
  • Page 25: Stage 1 Fans

    When the room temperature is below the room set point, the stage 1 fans run according to the stage 1 timer settings. Stage 1 timer: During TIME ON, the fans run at minimum speed. During TIME OFF, the fans do not run. TC4-2N6F.rev.07...
  • Page 26 1" (point 2), the stage 1 fans reach full speed. Above this tempera- ture, the controller continues to supply full speed voltage. However, a latch switch should cut off power to the stage 1 fans as the zone A or zone B curtains open for natural ventilation. TC4-2N6F.rev.07...
  • Page 27 1 - With a single minimum speed When a single minimum speed is specified and the minimum speed curve is deactivated (or the minimum speed curve is activated but not effec- tively operating), the fans run at this speed. TC4-2N6F.rev.07...
  • Page 28 When the minimum speed curve is activated, the controller adjusts the minimum speed every hour in a linear fashion between two consecu- tive points. TC4-2N6F.rev.07...
  • Page 29 (i.e. the controller will begin to adjust the minimum speed according to the specified points of the curve) only when the current day number of the temperature curve reaches the first day number of the minimum speed curve. TC4-2N6F.rev.07...
  • Page 30 Press push-button repeatedly until the word ON appears flash- ing on the display. Turn adjustment knob counterclockwise one notch. The word OFF appears flashing on the display, indicating that the mini- mum speed curve is now deactivated. TC4-2N6F.rev.07...
  • Page 31 10% per day. When the six points of the minimum speed curve have been specified, activate the minimum speed curve as described below (the minimum speed curve can be activated only if the temperature curve is acti- vated). TC4-2N6F.rev.07...
  • Page 32 TO ADJUST THE STAGE 1 BAND WIDTH Set the parameter selection knob to STAGE 1 - BAND WIDTH. The current band width appears flashing on the display. Using the adjustment knob, adjust the band width to the desired value. TC4-2N6F.rev.07...
  • Page 33: Stage 2 Fans

    2" (point 4), the stage 2 fans reach full speed. Above this temperature, the controller continues to supply full speed voltage. However, a latch switch should cut off power to the stage 2 fans as the zone A or zone B curtains open for natural ventilation. TC4-2N6F.rev.07...
  • Page 34 Using the adjustment knob, adjust the minimum speed to the desired value. Set the parameter selection knob to STAGE 2 - DIFFERENTIAL. The current differential appears flashing on the display. Using the adjustment knob, adjust the differential to the desired value. TC4-2N6F.rev.07...
  • Page 35: Stage 3 And 5 Fans

    When the room temperature rises to "room set point + band width 1 + 0.5°F (0.3°C) + differential 2 + differential 3 + curtain dead band + differential 5" (point 7), the stage 5 fans start to run. When the room temperature falls TC4-2N6F.rev.07...
  • Page 36 Using the adjustment knob, adjust the differential to the desired value. Press the push-button. The current differential for stage 5 alternates with the letters "d-5" on the display. Using the adjustment knob, adjust the differential to the desired value. TC4-2N6F.rev.07...
  • Page 37: Curtains

    1 + 0.5°F (0.3°C) + differential 2 + differential 3" (point 10), the zone B curtains begin to close according to the curtain timer settings and continue to do so until fully closed if the zone B temperature remains below this point. TC4-2N6F.rev.07...
  • Page 38 When the curtains close, the controller increases TIME ON by 5% for every degree that the outside set point exceeds the outside temperature and decreases TIME OFF by the same amount. The lower the outside temperature, the faster the curtains close. TC4-2N6F.rev.07...
  • Page 39 Using the adjustment knob, adjust the time on to the desired value. Press the push-button. The word OFF and the current time off alternately appear flashing on the display. Using the adjustment knob, adjust the time off to the desired value. TC4-2N6F.rev.07...
  • Page 40: Mist

    "room set point + band width 1 + 0.5°F (0.3°C) + differential 2 + differential 3 + curtain dead band + differential 5 + mist differential - 1°F (0.6°C)" (point 12), the mist stops operating. Mist timer: During TIME ON, the mist is on. During TIME OFF, the mist is off. TC4-2N6F.rev.07...
  • Page 41 Using the adjustment knob, adjust the time on to the desired value. Press the push-button. The word OFF and the current time off alternately appear flashing on the display. Using the adjustment knob, adjust the time off to the desired value. TC4-2N6F.rev.07...
  • Page 42: Heaters

    TO ADJUST THE HEATER DIFFERENTIAL The heater differential can be adjusted to 1°F(0.6°C) or 2°F(1.1°C): Set switch # 5 to ON to adjust the heater differential to 1°F (0.6°C). Set switch # 5 to OFF to adjust the heater differential to 2°F (1.1°C). TC4-2N6F.rev.07...
  • Page 43: Locking The Parameters

    Set switch # 1 to ON to lock the parameters. Set switch # 1 to OFF to unlock the parameters. FACTORY SETTING: When the controller is shipped from the factory, switch # 1 is set to OFF (the parameters are unlocked). TC4-2N6F.rev.07...
  • Page 44: Troubleshooting Guide

    "P" when connected improp- connection. the parameter erly. selection knob A room probe is Refer to "Defective Probes" is set to ROOM. defective. The defective A room probe is Refer to "defective probes" probe pilot light defective. is on. TC4-2N6F.rev.07...
  • Page 45 Adjust the minimum speed to a The minimum speed higher value. is too low. The fan motor is Check if the motor is defective defective. by connecting it to an alternate power supply. If it still is not operating, replace the motor. TC4-2N6F.rev.07...
  • Page 46 (N for 115V or L2 for 230V) to activate the motor. Also, be sure the stage 1 and 2 COMMON is supplied by line L1. TC4-2N6F.rev.07...
  • Page 47 The mist time on operating as are in minutes. Adjust the mist and time off were desired. time on and time off correctly. incorrectly adjusted. Adjust the mist differential There is a 1°F(0.6°C) accordingly. hysteresis on the mist. See "Mist". TC4-2N6F.rev.07...
  • Page 48: Technical Specifications

    MASTER BOX TC4-2N6F Supply: - 115/230 VAC (-18%,+8%), 60 Hz, overload and overvoltage protection fuse F6-1A fast blow. T50-2N6F Supply: - 115/230 VAC (-18%,+8%), 50 Hz, overload and overvoltage protection fuse F6-1A fast blow. - 12 VDC for AC back-up supply; can activate Stage 3, Stage 5 as well as curtains, mist and heaters if supplied with DC back-up voltage.
  • Page 49 C to 48.9 C). Accuracy: 1.8°F (1°C) between 41° and 95°F (5° and 35°C). Enclosure: ABS, moisture and dust-tight. The room temperature where the controller is installed MUST AT ALL TIMES REMAIN BETWEEN 32 AND 104 F (0 and 40 TC4-2N6F.rev.07...
  • Page 52 M 890-00146 rev. 07 REV. 01...