EXPERT LA
4.11 Test Mode
The test mode is used to simulate temperature
changes and to verify the controller's performances.
When the test is enabled, all outputs of the con-
troller operate according to the simulated tempera-
ture.
Select:
Main menu
Setup*
Test Mode
*
A password may be required to access this menu (sec. 4.2).
Test Mode
Temperature
•
First, set the simulated temperature to the
desired value then set the test mode status
to "On" to start the test.
The test automatically ends after
15 minutes of inactivity. It can also
end sooner by switching the test mode
status back to "Off".
Main menu
Setup
Test mode
Test mode
Off
72.3 °F
Use
to navigate
4.12 Version
This menu shows the version number of your con-
troller program. This piece of information is useful
to get technical support.
Select:
Main menu
Setup*
User
Version
*
A password may be required to access this menu (sec. 4.2).
SOFTWARE
EXPERT LA rev.00
Main menu
Setup
User
Version
EXPERT LA
VX.X
31