EXPERT LA
10.
RH COMPENSATION
The controller offers different way to compensate
for high/low relative humidity (RH) levels in the
room. All compensation functions are explained
below. To use them, you must enable each desired
compensation function in section 4.6.
•
High RH Compensation
with Heating Outputs:
When RH levels are too high, the controller
can activate heating outputs in timer mode.
As RH levels increase, the controller in-
creases the On Time portion of the heating
cycle to compensate for the change. The
maximum compensated heating On Time is
reached when RH levels are 10% above the
RH Set Point.
RH Comp. with
On Time of
Heating Outputs
the heaters'
Timer
Maximum
On Time
Minimum
On Time
Off
RH Set Point
•
High RH compensation with
cool cells & misting outputs:
If RH levels are too high, the controller can
stop the misting output and/or cool cell out-
put. Theses outputs are disabled when RH
levels reach the respective RH shutoff limit
of each output.
•
Low RH compensation
with misting outputs:
To compensate for low RH levels, the con-
troller can activate the misting output in
timer mode. The misting output starts when
RH levels decrease below the Low RH Set
Point.
RH (%)
EXPERT LA rev.00