Probe & Water Meter Calibration
You can slightly adjust the reading of each probe
input in order to obtain accurate and uniform read-
ings from all probes. In addition, if a water meter is
used, you must calibrate its water flow rate.
Select:
Main menu
Setup*
User
Prb Calib.
*
A password may be required to access this menu (sec. 4.2).
Adjust the reading of the probes (if required):
The probe calibration is common to all
programs of the controller.
Temperature probes (indoor & outdoor)
The reading of inside and outside tempera-
ture probes can be adjusted of ±3°F
(±1.7°C).
Relative humidity probe
The reading of inside and outside humidity
probes can be adjusted of ±3%.
Probe Calibration
Temperature Probe 1
Temperature Probe 2
Temperature Probe 3
Temperature Probe 4
Outside Probe 1
Outside Probe 2
Inside Humidity
Outside Humidity
Static Pressure
Water 1 Calibration
Water 2 Calibration
Water 3 Calibration
Use
to navigate
Static pressure probe
The reading of the static pressure probe can
be adjusted of±0.030"WC (±7Pa).
Water meter calibration
Specify the flow rate of each water meter.
It can be adjusted from 1 to 100 gallons (or
liters) per pulse.
EXPERT LA rev.00
Main menu
Setup
User
Prb calib
0.0 °F
0.0 °F
0.0 °F
0.0 °F
0.0 °F
0.0 °F
0 %
0 %
.000 "WC
1 g/p
1 g/p
1 g/p