Inlet Controller
TC5-ITA
USER'S MANUAL

Advertisement

Table of Contents
loading

Summary of Contents for Airstream TC5-ITA

  • Page 1 Inlet Controller TC5-ITA USER'S MANUAL...
  • Page 2: Table Of Contents

    Identification Numbers & End of Line Jumpers ......10 Comlink-2 Location & Connection ......... 12 Identifying Primary and Slave Units ........13 Seasonal Programs ............. 14 Verify TC5-ITA Operation (Manual Mode) ......14 TC5-ITA OPERATION ..........15 Basic Principle of Operation ..........15 Calibration ................ 18 CONTROLLER FUNCTIONS .........
  • Page 3: Precautions

    Pay attention. The following text contains useful information. FOR CUSTOMER USE Enter below the serial number located on the side of the controller and retain this information for future reference. TC5-ITA Model number: Serial number: TC5-ITA rev.02...
  • Page 4: Features

    FEATURES The TC5-ITA is an electronic device used for air inlet control in livestock buildings. In combination with an environment controller, the TC5-ITA coordinates the movement of the air inlets with the operation of the fans using the real-time clock. Additional units can be connected to the TC5-ITA for an independent control of additional air inlets.
  • Page 5: Location Of The Controls

    CALIBRATION Turns on when the c ontroller is in calibration m ode. MANUAL Turns on when the actuator is controlled in m anual mode. INLET RESET Turns on when the inlet position is being reset. TC5-ITA rev.02...
  • Page 6: Internal Switches

    AUTO RESET THE INLET POSITION RESET MIN POSITION ONLY RESET TOWARD THE NEAREST POSITION STOP THE MANUAL RESET START THE MANUAL RESET AM/PM TIME FORMAT 24 HOUR FORMAT OPENING = TIME VALUE OPENING = % INLET MODE TUNNEL MODE TC5-ITA rev.02...
  • Page 7: Installation Procedure

    Integrating an air inlet control system into your ventilation system requires the following equipment: • A Comlink-2 communication module added to your controller • A TC5-ITA controller for each air inlet panel (up to 100 in all) • An alarm system (optional) • A DC power supply (optional) •...
  • Page 8 TC5-ITA TC5-ITA rev.02...
  • Page 9 AND EQUIPMENT DAMAGE. TEMPERATURE PROBES: If your TC5-ITA unit is supplied with a temperature probe, connect it to the PROBE terminal and set internal switch #5 to ON. Note that the TC5-ITA can run without a temperature sensor; in this case, the ROOM TEMPERATURE menu will not be a available.
  • Page 10: Identification Numbers & End Of Line Jumpers

    JUMPERS The TC5-ITA network operates on two communication lines. One line links the TC5-ITA units together to the main controller and the other line links temperature controllers to a computer (this second line is optional). Two jumpers on the Comlink-2 card are used to identify the end of line for each communication line.
  • Page 11 TC5-ITA INLET INLET INLET MAIN CONTROLLER CONTROLLER CONTROLLER ENVIRONMENT (MASTER) (SLAVE) (SLAVE) CONTROLLER ADDITIONAL CONTROLLER ADDITIONAL CONTROLLER TC5-ITA rev.02...
  • Page 12: Comlink-2 Location & Connection

    (see illustration beside). For com- munication, always use a 1 twisted pair shielded cable. The maximum length of the cable is 3000m and the recom- mended wire diameter is 1.0 mm. Use a lightning protection module when running the cable between buildings. TC5-ITA rev.02...
  • Page 13: Identifying Primary And Slave Units

    Identifying Primary and Slave Units If your installation requires more than one TC5-ITA unit for independent control of different air inlets, one of the TC5-ITA will be configured as the primary unit and the others will be configured as slaves. Up to 99 slave units can be connected in this way.
  • Page 14: Seasonal Programs

    Make sure to select the right season is selected before making changes to the parameters. Verify TC5-ITA Operation (Manual Mode) • Power the TC5-ITA then select MANUAL MODE using the func- tion selection buttons. • Use the adjustment buttons to select the desired actuator status: select "OPEn"...
  • Page 15: Tc5-Ita Operation

    SET POINT Inlet & Tunnel Modes: When the last reference point is reached, the TC5-ITA can either open the air inlet according to a user-defined value (internal switch #12 to OFF), or it can fully open the air inlet up until the inlet reaches its limit switch (internal switch #12 to ON).
  • Page 16 100 %. During a Variable Stage with 0 Intermediate Step Opening (Time or %) The three following graphs illustrate when each inter- Step HI mediate step starts. Opening Step Opening Variable Stage Speed 50 % 100 % TC5-ITA rev.02...
  • Page 17 Opening Intermediary Step 2 Intermediary Step 1 Step Opening Variable Stage Speed 50 % 60 % 85 % 100 % (interm. (interm. step1) step2 Refer to the PROGRAMMING chapter to enable the proper number of intermediate opening steps. TC5-ITA rev.02...
  • Page 18: Calibration

    TC5-ITA Calibration The TC5-ITA adjusts the opening of air inlets according to the ventilation stages provided by the environment controller. The calibration allows TC5-ITA units to detect how many On/Off and variable stages the environ- ment controller uses. When the calibration is launched on the PRIMARY TC5-ITA unit, the envi- ronment controller enters in test mode and starts simulating the room tem- perature.
  • Page 19 TC5-ITA unit to start the calibration. 3. Once the calibration is launched, press and hold the right-arrow key for 2 seconds on all TC5-ITA slave units within the next 30 sec- onds. 4. After 30 seconds, the environment controller enters in test mode and starts simulating the room temperature.
  • Page 20: Controller Functions

    Use the adjustment buttons to set the hours to the desired value. Identification Number This function displays the identification number of the TC5-ITA along with its primary/slave status. The identification number is set using jumpers on the COMLINK-2 communication card (see INSTALLATION PROCEDURE chapter).
  • Page 21: Total Opening Time

    • Proceed in similar fashion to set the total opening time on all TC5-ITA units. Opening Display The user must assign an inlet position to each ventilation stage. This posi- tion can either be specified as a moving time of the actuator or as a per- centage of the total run time.
  • Page 22: Programming Inlet Openings

    • Enter the total opening time of the inlet of each TC5-ITA unit. PROGRAMMING INLET OPENINGS: • Select "PROGRAMMING" using the function selection buttons (note that this menu is not available during the calibration) The opening time or the inlet position (in %) associated with step 0 is displayed.
  • Page 23: Remaining Run Time / Opening Menu

    The letters "STOP" are dis- played if the inlet is not moving. If the inlet opening is displayed as a percentage, the REMAINING RUN TIME / OPENING menu shows the current opening (in %) of the air inlet. TC5-ITA rev.02...
  • Page 24: Resetting The Inlet Position

    Set internal switch #8 to ON to use this reset method. This resetting method requires the pres- ence of limit switches at both ends of the actuator. TC5-ITA rev.02...
  • Page 25 • Proceed in similar fashion to set the Reset Delay on all TC5-ITA units. Manual & Automatic Resets The reset of an inlet can either be performed manually (which is useful when the user detects an offset in the inlet position) and/or it can be per- formed at regular intervals (auto-reset).
  • Page 26 Use the adjustment buttons to set the frequency to the desired value. The frequency can be adjusted once every 1 to 7 days. Se- lect "1" to reset the position every day; select "2" to reset the position every 2 days, etc. TC5-ITA rev.02...
  • Page 27: Temperature Alarms

    It can be adjusted from 0.5°F to 40°F (0.3°C to 22.2°C). Note that internal switch #4 must be set to ON for this alarm to be detected. TEMPERATURE HI TEMPERATURE ALARM SET POINT LO TEMPERATURE ALARM TIME TC5-ITA rev.02...
  • Page 28 Use the adjustment buttons to adjust the Lo Offset to the desired value. • Press the right-arrow key once. The Hi Offset flashes on the dis- play alternating with the letters "Hi". • Use the adjustment buttons to adjust the Hi Offset to the desired value. TC5-ITA rev.02...
  • Page 29: Alarms - Readout

    TC5-ITA Alarms - Readout When an alarm occurs, the TC5-ITA activates the alarm contact and turns on the alarm pilot light. The alarm readout function displays all currently outstanding alarm situations. • Select "ALARM READOUT" using the function selection buttons.
  • Page 30: Room Temperature

    "Hi". • Press the adjustment buttons' down-arrow key once. The current room temperature is displayed once again. • Press the adjustment buttons' down arrow-key once again. The minimum temperature value is displayed alternating with the let- ters "Lo". TC5-ITA rev.02...
  • Page 31: Troubleshooting Guide

    THE TC5-ITA IS DEFECTIVE. - LISTEN TO SEE IF THERE IS A CLICKING SOUND WHEN THE ALARM PILOT LIGHT TURNS ON. IF THERE IS NO CLICKING SOUND, THE TC5-ITA IS DEFECTIVE. CONTACT YOUR DISTRIBUTOR TO REPAIR THE CONTROLLER. TC5-ITA rev.02...
  • Page 32: Technical Specifications

    -40.0° to 120.0°F(-40.0° to 49°C). Accuracy: 1.8 F (1°C) between 41 and 95 F (5° and 35°C). Enclosure: ABS, humidity and dust-tight. The room temperature where the controller is located MUST ALWAYS REMAIN BETWEEN 32 AND 104 F (0 AND 40 For indoor use. TC5-ITA rev.02...
  • Page 33: Index

    Keys 5 ID number 10 Model number 3 Mounting instructions 7 Primary / slave modules Leds 5 Principle of operation 13 Limit switch positionning 14 Settings 6 Serial number 3 Setup 8 Status leds 5 Technical specifications 32 TC5-ITA rev.02...
  • Page 34 Reset Activation 6 Principle of operation 24 Settings 25–26 Seasonal program selection 6, 14 Sensors see Probes Serial number 3 Slave unit Principle of operation 13 Settings 6 Summer program 6 Technical specifications 32 Temperature Room temperature 30 TC5-ITA rev.02...
  • Page 36 M 890-00047 rev. 02 REV. 00...