 Cable gauge of main circuit terminals and earth (ground) terminals
Use an appropriate cable gauge to suppress the voltage drop to 2% or less.
If the wiring distance is long between the inverter and motor, the voltage drop in the main circuit will cause the motor torque to decrease especially at a low speed.
The following table indicates a selection example for the wiring length of 20 m.
• 200 V class (220 V input power supply, 150% overload current rating for 1 minute)
Terminal
Applicable inverter
screw
model
size

FR-A820-00046(0.4K) to
M4
1.5
00167(2.2K)
FR-A820-00250(3.7K)
M4
1.5
FR-A820-00340(5.5K)
M5(M4)
2.5
FR-A820-00490(7.5K)
M5(M4)
2.5
FR-A820-00630(11K)
M5
2.5
FR-A820-00770(15K)
M6
4.4
FR-A820-00930(18.5K)
M8(M6)
7.8
FR-A820-01250(22K)
M8(M6)
7.8
FR-A820-01540(30K)
M8(M6)
7.8
FR-A820-01870(37K)
M10(M8)
14.7
FR-A820-02330(45K)
M10(M8)
14.7
FR-A820-03160(55K)
M12(M8)
24.5
FR-A820-03800(75K)
M12(M8)
FR-A820-04750(90K)
M12(M8)
24.5
• 400 V class (440 V input power supply, 150% overload current rating for 1 minute)
Terminal
Applicable inverter
screw
model
size

FR-A840-00023(0.4K) to
M4
1.5
00126(3.7K)
FR-A840-00170(5.5K)
M4
1.5
FR-A840-00250(7.5K)
M4
1.5
FR-A840-00310(11K)
M5
2.5
FR-A840-00380(15K)
M5
2.5
FR-A840-00470(18.5K)
M6
4.4
FR-A840-00620(22K)
M6
4.4
FR-A840-00770(30K)
M6
4.4
FR-A840-00930(37K)
M8
7.8
FR-A840-01160(45K)
M8
7.8
FR-A840-01800(55K)
M8
7.8
FR-A840-02160(75K)
M10
14.7
FR-A840-02600(90K)
M10
14.7
FR-A840-03250(110K)
M10(M12)
14.7
FR-A840-03610(132K)
M10(M12)
14.7
FR-A840-04320(160K)
M12(M10)
24.5
FR-A840-04810(185K)
M12(M10)
24.5
FR-A840-05470(220K)
M12(M10)
46
FR-A840-06100(250K)
M12(M10)
46
FR-A840-06830(280K)
M12(M10)
46

For FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower, this cable gauge is with the continuous maximum permissible temperature of 75°C (HIV cable
(600 V class 2 vinyl-insulated cable), etc.). Assumes that the surrounding air temperature is 50°C or less and the wiring distance is 20 m or less.
For FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher, this cable gauge is with the continuous maximum permissible temperature of 90°C or higher
(LMFC (heat resistant flexible cross-linked polyethylene insulated cable), etc.). Assumes that the surrounding air temperature is 50°C or less and the wiring is in-
enclosure.

For all the 200 V class capacities and FR-A840-01160(45K) or lower, this cable gauge is with the continuous maximum permissible temperature of 75°C (THHW cable).
This is assumes a surrounding air temperature of 40°C or less and wiring distance of 20 m or less.
For FR-A840-01800(55K) or higher, this cable gauge is with continuous maximum permissible temperature of 90°C (THHN cable). This assumes a surrounding air
temperature of 40°C or lower and in-enclosure wiring.
(For the use in the United States or Canada, refer to

For FR-A820-00770(15K) or lower and FR-A840-01160(45K) or lower, the cable gauge is with the continuous maximum permissible temperature of 70°C (PVC cable).
This assumes a surrounding air temperature of 40°C or less and wiring distance of 20 m or less.
For FR-A820-00930(18.5K) or higher and FR-A840-01800(55K) or higher, this cable gauge is with continuous maximum permissible temperature of 90°C (XLPE cable).
This assumes a surrounding air temperature of 40°C and in-enclosure wiring.

The terminal screw size indicates the size of the terminal screw for R/L1, S/L2, T/L3, U, V, W, PR, PX, P/+, N/-, P1, P3, and the screw for earthing (grounding).
The screw size for PR and PX terminals of FR-A820-00340(5.5K) and FR-A820-00490(7.5K) is indicated in parentheses.
The screw size for earthing (grounding) of FR-A820-00930(18.5K) or higher is indicated in parentheses.
The screw size for P/+ terminal for connecting an option to FR-A840-03250(110K) or FR-A840-03610(132K) is indicated in parentheses.
The screw size for earthing (grounding) of FR-A840-04320(160K) or higher is indicated in parenthesis.
The line voltage drop can be calculated by the following formula:
Line voltage drop [V] =
wire resistance [mΩ/m]
×
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque reduction) in the low speed range.
NOTE
• The selection example is for the ND rating. For selecting the SLD rating, LD rating, or HD rating, refer to the Instruction Manual (Detailed).
• Tighten the terminal screw to the specified torque. A screw that has been tightened too loosely can cause a short circuit or malfunction. A screw that has been
tightened too tightly can cause a short circuit or malfunction due to the unit breakage.
• Use crimp terminals with insulation sleeves to wire the power supply and motor.
Crimp terminal
Tightening
R/L1,
R/L1,
torque N•m
S/L2,
U, V, W
S/L2,
T/L3
T/L3
2-4
2-4
2
5.5-4
5.5-4
3.5
5.5-5
5.5-5
5.5
14-5
8-5
14
14-5
14-5
14
22-6
22-6
22
38-8
22-8
38
38-8
38-8
38
60-8
60-8
60
80-10
60-10
80
100-10
100-10
100
100-12
100-12
100
24.5
150-12
150-12
125
150-12
150-12
150
Crimp terminal
Tightening
R/L1,
R/L1,
torque N•m
S/L2,
U, V, W
S/L2,
T/L3
T/L3
2-4
2-4
2
2-4
2-4
2
5.5-4
5.5-4
3.5
5.5-5
5.5-5
5.5
8-5
5.5-5
8
14-6
8-6
14
14-6
14-6
14
22-6
22-6
22
22-8
22-8
22
38-8
38-8
38
60-8
60-8
60
60-10
60-10
60
60-10
60-10
60
80-10
80-10
80
100-10
100-10
100
150-12
150-12
125
150-12
150-12
150
100-12
100-12
2×100
100-12
100-12
2×100
150-12
150-12
2×125
page
35.)
wiring distance [m]
×
Cable gauge
2
HIV cables, etc. (mm
)

Earthing
P/+,
U, V, W
(grounding)
P1
cable
2
2
2
14
3.5
3.5
3.5
12
5.5
5.5
5.5
10
8
14
5.5
6
14
14
8
6
22
22
14
4
22
38
14
2
38
38
22
2
60
60
22
1/0
60
80
22
3/0
100
100
38
4/0
100
100
38
4/0
125
125
38
250
150
150
38
300
Cable gauge
2
HIV cables, etc. (mm
)

Earthing
P/+,
U, V, W
(grounding)
P1
cable
2
2
2
14
2
3.5
3.5
12
3.5
3.5
3.5
12
5.5
5.5
5.5
10
5.5
8
5.5
8
8
14
8
6
14
22
14
6
22
22
14
4
22
22
14
4
38
38
22
1
60
60
22
1/0
60
60
22
1/0
60
80
22
3/0
80
80
22
3/0
100
100
38
4/0
125
150
38
250
150
150
38
300
2×100
2×100 60
2×4/0
2×100
2×125 60
2×4/0
2×125
2×125 60
2×250
current [A] / 1000
×
Main circuit terminals
AWG/MCM
PVC cables, etc. (mm

R/L1,
R/L1,
S/L2,
U, V, W
S/L2,
U, V, W
(grounding)
T/L3
T/L3
14
2.5
2.5
2.5
12
4
4
4
10
6
6
6
8
16
10
16
6
16
16
16
4
25
25
16
4
35
25
25
2
35
35
25
1/0
50
50
25
1/0
70
70
35
4/0
95
95
50
4/0
95
95
50
250
120
120
300
150
150
AWG/MCM
PVC cables, etc. (mm

R/L1,
R/L1,
S/L2,
U, V, W
S/L2,
U, V, W
(grounding)
T/L3
T/L3
14
2.5
2.5
2.5
14
2.5
2.5
4
12
4
4
4
10
6
6
10
10
10
6
10
8
16
10
16
6
16
16
16
4
25
25
16
4
25
25
16
2
50
50
25
1/0
50
50
25
1/0
50
50
25
3/0
50
50
25
3/0
70
70
35
4/0
95
95
50
250
120
120
70
300
150
150
95
2×4/0
2×95
2×95
95
2×4/0
2×95
2×95
95
2×250
2×120
2×120
120