Safety stop function
 Hubs
Use hubs that meet the conditions listed below:
• Compliance with the IEEE802.3 (1000BASE-T)
• Support of the auto MDI/MDI-X function
• Support of the auto-negotiation function
• Switching hub (layer 2 switch)

A repeater hub is not available.
Operation is not guaranteed if the hubs do not meet these conditions.
Industrial switching hub
Type
NZ2EHG-T8
 Ethernet cable connection
• Connect or remove an Ethernet cable after switching the power of the inverter OFF.
• PORT1 and PORT2 do not need to be distinguished.
• When only one connector is used in star topology, either PORT1 or PORT2 is applicable.
• When using two connectors for line topology and ring topology, an Ethernet cable can be connected to the connectors in any combination. For example,
the cable can be connected between PORT1s or between PORT1 and PORT2.
Connection between
PORT1 and PORT1, PORT2 and PORT2
Connector
Connector
for
communication
communication
(PORT2)
NOTE
• Ethernet is a registered trademark of Xerox Corporation of the United States.
• For the details of the CC-Link IE Field Network, refer to the FR-A800 Instruction Manual (Detailed).
2.5
Safety stop function
 Function description
The terminals related to the safety stop function are shown below.
Terminal
symbol
S1
For input of the safety stop channel 1.

S2
For input of the safety stop channel 2.

SIC
Common terminal for terminals S1 and S2.

Outputs when an alarm or failure is detected.
So (SO)
The signal is output when no internal safety circuit
failure
exists.

SOC
Terminal So (SO) ( open collector output ) common

In the initial status, terminals S1 and PC, S2 and PC, and SIC and SD are respectively shorted with shorting wires. To use the safety stop function, remove all the
shorting wires, and then connect to the safety relay module as shown in the following connection diagram.

At an internal safety circuit failure, the operation panel displays one of the faults shown on the next page.
NOTE
• Use terminal So (SO) to output a fault and to prevent restarting of the inverter. The signal cannot be used as safety stop input signal to other devices.
14
WIRING

Mitsubishi Electric Corporation
Connector
Connector
for
for
for
communication
communication
(PORT1)
(PORT2)
(PORT1)
To the next
connector for
communication
(PORT2)
Terminal function description
Open between S1 and SIC, and between S2 and SIC:
In safety stop mode.
Short: Other than the safety stop mode.
OFF: Internal safety circuit failure
ON: No internal safety circuit failure
Manufacturer
Connection between
PORT1 and PORT2
Connector
Connector
for
for
communication
communication
(PORT2)
(PORT1)


Connector
Connector
for
for
communication
communication
(PORT2)
(PORT1)
To the next
connector for
communication
(PORT2)

Advertisement

loading