 Monitoring I/O terminals on the operation panel (FR-DU08) (Pr.52,
Pr.774 to Pr.776, Pr.992)
• When Pr.52 (Pr.774 to Pr.776, Pr.992) = "55", the I/O terminal state can be monitored on the operation panel (FR-DU08).
• When a terminal is ON, the corresponding LED segment is ON. The center LED segments are always ON.
Pr.52, Pr.774 to Pr.776,
Pr.992 setting
55
• On the I/O terminal monitor, the upper LEDs indicate the input terminal status, and the lower LEDs indicate the output terminal
status.
STP (STOP)
AU
RM
RH
RT
RL
OL
RUN
ABC1
SU
ABC2
IPF
6
Main circuit capacitor life measuring
The measurement of the main circuit capacitor life can start whenever the power supply is turned OFF without setting
the parameter every time.
Pr.
Name
259
Main circuit capacitor life
E704
measuring

*1
The setting is available only for standard models and IP55 compatible models.
 Life display of the main circuit capacitor (Pr.258, Pr.259) (Standard
models and IP55 compatible models)
• For accurate life measurement of the main circuit capacitor, wait three hours or longer after turning OFF. The
temperature left in the main circuit capacitor affects measurement.
Monitor item
I/O terminal status
JOG
RES
STF
CS
STR
S2
MRS
FU
So (SO)
Initial
value
0
Displays the I/O terminal ON/OFF state of the inverter.
Segments corresponding
S1
to input terminals
The center LED segments are
always ON.
Segments corresponding
to output terminals
Setting range
0
No measurement
Setting "1" and turning the power supply OFF starts the
measurement of the main circuit capacitor life. (Only once)
1 (2, 3, 8, 9)
If the setting value of Pr.259 becomes "3" after turning the power
supply ON again, it means that the measurement is completed. The
deterioration degree is read to Pr.258.
When "11" is set, turning OFF the power supply starts the
measurement of the main circuit capacitor life.
11 (12, 13, 18,
If the setting value of Pr.259 becomes "13" after turning the power
19)
supply ON again, it means that the measurement is completed. The
deterioration degree is read to Pr.258.
7
Monitor description
- Display example -
When signals STF,
RH and RUN are on
Description
BCN-C22005-906
A