Setting
Pr.
Name
range
0.1 to 1000%,
129
PID proportional band
9999
0.1 to 3600s,
130
PID integral time
9999
131
PID upper limit
0 to 100%, 9999 9999
132
PID lower limit
0 to 100%, 9999 9999
133
PID action set point
0 to 100%, 9999 9999
0.01 to 10s,
134
PID differential time
9999
Electronic bypass
135
0, 1
sequence selection
MC switchover interlock
136
0 to 100s
time
137
Start waiting time
0 to 100s
Bypass selection at a
138
0, 1
fault
Automatic switchover
139
frequency from inverter
0 to 60Hz, 9999 9999
to bypass operation
Backlash acceleration
140
0 to 590Hz
stopping frequency
Backlash acceleration
141
0 to 360s
stopping time
Backlash deceleration
142
0 to 590Hz
stopping frequency
Backlash deceleration
143
0 to 360s
stopping time
0, 2, 4, 6, 8, 10,
Speed setting
12, 102, 104,
144
switchover
106, 108, 110,
112
PU display language
145
0 to 7
selection
Acceleration/
147
deceleration time
0 to 590Hz, 9999
switching frequency
Stall prevention level at
148
0 to 400%
0 V input
Stall prevention level at
149
0 to 400%
10 V input
Output current
150
0 to 400%
detection level
Output current
151
detection signal delay
0 to 10s
time
Zero current detection
152
0 to 400%
level
Zero current detection
153
0 to 10s
time
Voltage reduction
154
selection during stall
0, 1, 10, 11
prevention operation
RT signal function
155
validity condition
0, 10
selection
Stall prevention
156
0 to 31, 100, 101 0
operation selection
157
OL signal output timer
0 to 25s, 9999
1 to 3, 5 to 14,
17, 18, 21, 24,
AM terminal function
32 to 34, 36, 46,
158
selection
50, 52 to 54, 61,
62, 67, 70, 
87 to 98
Automatic switchover
frequency range from
159
0 to 10Hz, 9999 9999
bypass to inverter
operation
160
User group read
0, 1, 9999
selection

Frequency setting/key
161
0, 1, 10, 11
lock operation selection
Automatic restart after
0 to 3, 10 to 13,
162
instantaneous power
1000 to 1003,
failure selection
1010 to 1013
First cushion time for
163
0 to 20s
restart
First cushion voltage for
164
0 to 100%
restart
Stall prevention
165
operation level for
0 to 400%
restart
Output current
166
detection signal
0 to 10s, 9999
retention time
Output current
167
detection operation
0, 1, 10, 11
selection
168
Parameter for manufacturer setting. Do not set.
169
170
Watt-hour meter clear
0, 10, 9999
Operation hour meter
171
0, 9999
clear
User group registered
172
9999, (0 to 16)
display/batch clear
173
User group registration 0 to 1999, 9999
174
User group clear
0 to 1999, 9999
Initial
Pr.
Name
value
STF terminal function
100%
178
selection
STR terminal function
1s
179
selection
RL terminal function
180
selection
RM terminal function
181
selection
9999
RH terminal function
182
selection
0
RT terminal function
183
selection
1s
AU terminal function
184
selection
0.5s
JOG terminal function
185
selection
0
CS terminal function
186
selection
MRS terminal function
187
selection
1Hz
STOP terminal function
188
selection
0.5s
RES terminal function
189
selection
1Hz
RUN terminal function
190
selection
0.5s
SU terminal function
191
selection
IPF terminal function
4
192
selection
OL terminal function
193
selection
FU terminal function
194
selection
9999
ABC1 terminal function
195
selection
150%
ABC2 terminal function
196
selection
200%
232 to
Multi-speed setting (8
239
speed to 15 speed)
150%
Soft-PWM operation
240
selection
0s
Analog input display
241
unit switchover
5%
Terminal 1 added
242
compensation amount
(terminal 2)
0.5s
Terminal 1 added
243
compensation amount
1
(terminal 4)
Cooling fan operation
244
selection
0
245
Rated slip
Slip compensation time
246
constant
Constant-power range
0s
247
slip compensation
selection
Self power
248
management selection 0 to 2
1
Earth (ground) fault
249
detection at start
250
Stop selection
Output phase loss
251
protection selection
0
252
Override bias
253
Override gain
0
Main circuit power OFF
254
waiting time
0
Life alarm status
255
display
0s
Inrush current limit
256
circuit life display
0%
Control circuit capacitor
257
life display
Main circuit capacitor
150%
258
life display
Main circuit capacitor
259
life measuring
0.1s
PWM frequency
260
automatic switchover
0
Power failure stop
261
selection
Subtracted frequency at
262
deceleration start
Subtraction starting
9999
263
frequency
9999
Power-failure
264
deceleration time 1
0
Power-failure
265
deceleration time 2
9999
Power failure
9999
266
deceleration time
switchover frequency
Setting
Initial
Pr.
range
value
Terminal 4 input
60
267
selection
Monitor decimal digits
61
268
selection
269
Parameter for manufacturer setting. Do not set.
0
Stop-on contact/load
torque high-speed
1
270
frequency control
0 to 20,
selection
2
22 to 28, 32, 37,
High-speed setting
42 to 48, 
271
maximum current
50 to 53, 
3
Middle-speed setting
57 to 62,
272
minimum current
64 to 74,
4
76 to 80, 85, 
Current averaging
273
87 to 89
range
92 to 96,
5
Current averaging filter
9999

274
time constant
6
Stop-on contact
275
excitation current low-
24
speed multiplying factor
PWM carrier frequency
276
25
at stop-on contact
Brake opening
62
278
frequency
0 to 8, 10 to 20, 22,
279
Brake opening current
0
25 to 28, 30 to 36,
Brake opening current
280
38 to 57, 60, 61, 63,
detection time
64, 67, 68, 70, 79,
1
Brake operation time at
80, 84, 85, 90 to 99,
281
start
100 to 108,
2
110 to 116, 120,
Brake operation
282
122, 125 to 128,
frequency
130 to 136,
3
Brake operation time at
138 to 157, 160,
283
stop
161, 163, 164, 167,
168, 170, 179, 180,
4
Deceleration detection
284
184, 185,
function selection
190 to 199,
Overspeed detection
99
200 to 208,
frequency (Excessive
211 to 213,
285
speed deviation
300 to 308,
9999
detection frequency)
311 to 313, 9999

286
Droop gain
0 to 590Hz, 9999
9999
287
Droop filter time constant 0 to 1s
Droop function
288
0, 1
1
activation selection
Inverter output terminal
0, 1
0
289
filter
Monitor negative output
290
selection
0 to 100%
100%
291
Pulse train I/O selection
0 to 100%
75%
Automatic acceleration/
0, 1, 101 to 105
1
292
deceleration
0 to 50%, 9999 9999
Acceleration/deceleration
293
separate selection
0.01 to 10s
0.5s
UV avoidance voltage
294
gain
0, 9999
9999
Frequency change
295
increment amount
setting
0
296
Password lock level
0, 1
0
0 to 100s, 
297
Password lock/unlock
1000 to 1100s,
9999
8888, 9999
Frequency search gain 0 to 32767,
298
0, 1
1
Rotation direction
0 to 200%
50%
299
detection selection at
0 to 200%
150%
restarting
1 to 3600s,
600s
313
DO0 output selection
9999

(0 to 15)
0
314
DO1 output selection

(0 to 100%)
100%
315
DO2 output selection

(0 to 100%)
100%
316
DO3 output selection

(0 to 100%)
100%
317
DO4 output selection

0, 1
0
318
DO5 output selection

0, 1
1
319
DO6 output selection

0 to 2, 11, 12,
0
21, 22
320
RA1 output selection

0 to 20Hz
3Hz
321
RA2 output selection

0 to 590Hz,
60/50Hz

9999
0 to 3600s
5s
322
RA3 output selection

0 to 3600s,
9999
RS-485 communication
9999
331
station number
0 to 590Hz
60/50Hz

RS-485 communication
332
speed
Parameter list
Setting
Initial
Name
range
value
0 to 2
0
0, 1, 9999
9999
0 to 3, 11, 13
0
0 to 400%
50%
0 to 400%
100%
0 to 590Hz,
9999
9999
1 to 4000
16
0 to 300%, 9999 9999
0 to 9, 9999

9999
0 to 4, 9999

0 to 30Hz
3Hz
0 to 400%
130%
0 to 2s
0.3s
0 to 5s
0.3s
0 to 30Hz
6Hz
0 to 5s
0.3s
0, 1
0
0 to 30Hz, 9999 9999
0 to 100%
0%
0.3s
0 to 2, 10, 11, 
0
20 to 22
5 to 50ms, 9999 9999
0 to 7
0
0, 1, 10, 11, 20,
21, 100
0
(FM type)
0, 1 (CA type)
0, 1, 3, 5 to 8, 11
0
0 to 2
0
0 to 200%
100%
0, 0.01, 0.10,
0
1.00, 10.00
0 to 6, 99, 
100 to 106, 199,
9999
9999
(0 to 5), 
1000 to 9998,
9999
9999
9999
9999
0, 1, 9999
0
0 to 8, 10 to 20, 22,
9999
25 to 28, 30 to 36, 
38 to 57, 60, 61, 63,
9999
64, 68, 70, 79, 
84 to 99, 100 to 108,
110 to 116, 120,
9999
122, 125 to 128, 
130 to 136, 
9999
138 to 157, 160,
161, 163, 164, 168,
170, 179, 
9999
184 to 199, 
200 to 208, 
9999
211 to 213, 
300 to 308, 
9999
311 to 313, 9999
0 to 8, 10 to 20,
22, 25 to 28, 
9999
30 to 36, 
38 to 57, 60, 61,
63, 64, 68, 70,
9999
79, 80, 84 to 91,
94 to 99, 
200 to 208, 
9999
211 to 213,
9999
0 to 31 (0 to
0
247)
3, 6, 12, 24, 48,
96, 192, 384,
96
576, 768, 1152
21
BASIC OPERATION