Figure 36: Status > Modules > Output - Gamatronic POWER+ PREMIUM Installation Manual

Table of Contents

Advertisement

If the output voltage of one or more phases is not within 2 % of the system nominal output voltage,
then:
12.1
Navigate to "Setup > Modules > Ac output voltage adjustment".
12.2
Select the replacement module, and adjust the problematic phases up or down as required.
12.3
Return to step 12 and repeat the verification and adjustment process until the output voltage
of each phase of the replacement module is within 2 % of the system nominal value.
.
13
Navigate to the main menu screen. If the yellow, triangular alarm indicator is visible, check the
alarms and see if any of them are related to the new module. If there are no alarms, you have
successfully replaced the module.
36
G
E
AMATRONIC
LECTRONIC
Figure 36: Status > Modules > Output
I
L
.
NDUSTRIES
TD
Power + PREMIUM, Installation Guide, rel. 1.7