Gamatronic POWER+ PREMIUM Installation Manual page 62

Table of Contents

Advertisement

SYSTEM CONTROLLER – TECHNICAL DATA
Display
Other indicators
Analog input channels
Real Time Clock (RTC)
Power meter
Volt-free outputs (dry contacts)
Communication
Communications with system modules
Events log
System operation without controller
On-screen parameters
Alarms
RTC operation without power
Power requirements
Remote monitoring panel
54
G
E
I
AMATRONIC
LECTRONIC
NDUSTRIES
LCD flat panel, touch-sensitive
Audible alarm
4 input dry contacts (N.O. / N.C.)
Yes, with backup
kVA, kW, PF
6 outputs, rated 50 V / 1 A
TCP/IP, GPRS/SMS wireless communications
(optional)
Serial, isolated
500 events
Unchanged
Load bar-graph
3-phase voltages
3-phase currents
Battery voltage
Status of each UPS module
Static-switch parameters and status
Battery sensor temperature
Ac failure
Dc failure
UPS module(s) failure
Load on bypass
Battery test failure
Over/under temperature
Overload
Or any of over 40 other alarms
(Contacts rated max. 48 V 1 A)
Unlimited
3 × 400 Vac (40 W) and 405 Vdc
Displays 10 LED indicators
Load level indicators
Audible alarm
L
.
TD
Power + PREMIUM, Installation Guide, rel. 1.7

Advertisement