Figure 40: Status > Modules > Output - Gamatronic POWER+ PREMIUM Installation Manual

Table of Contents

Advertisement

If the output voltage of one or more phases is not within 2 % of the system nominal output voltage,
then:
7.1
Navigate to "Setup > Modules > Ac output voltage adjustment".
7.2
Select the replacement module, and adjust the problematic phases up or down as required.
7.3
Return to step 7 and repeat the verification and adjustment process until the output voltage
of each phase of the replacement module is within 2% of the system nominal value.
.
8
The Power+ Premium controller must be informed that a new module has been added to the
system. On the LCD control panel, from the main menu navigate to
"Setup > System > Number of modules". Increase the total number of modules by one, and if the
modules is to be one of the redundant modules, increase the number of redundant modules by one.
.
Navigate to the main menu screen. If the yellow, triangular "alarm" indicator is visible, check the
9
alarms and see if any of them are related to the new module. If there are no related alarms, the
module has been successfully added to the system.
Power + PREMIUM, Installation Guide, rel. 1.7
G
E
AMATRONIC
LECTRONIC
Figure 40: Status > Modules > Output
I
L
.
NDUSTRIES
TD
39