Occupancy Sensing - Crestron iLux CLS-C6 Operation Manual

Crestron cls-c6 integrated lighting system: operations guide
Hide thumbs Also See for iLux CLS-C6:
Table of Contents

Advertisement

iLux
Lighting System
Lights Mode
• iLux
34
Lighting System: CLS/CLSI-C6 & CLS/CLSI-C6M
Crestron CLS/CLSI-C6 & CLS/CLSI-C6M

Occupancy Sensing

Occupancy sensing may have specific actions specified for entry and for exit. Either
or both of these may be disabled. A limited number of actions are available when
programmed locally; more options are available when programmed using the iLux
Designer program.
If motion is detected, or some other activity takes place, a room is considered
occupied. If no activity takes place for a specified time (default is 30 minutes), the
room is considered unoccupied.
When the state of the room changes from occupied to unoccupied, the exit function
(if enabled) will be executed. When the state of the room changes from unoccupied
to occupied, due to motion detection, the entry function (if enabled) will be executed.
When the state of the room changes from unoccupied to occupied due to a button
press or the receipt of a command, no function will be executed.
NOTE: In systems with multiple CLS-C6 units that have the motion sensor function
enabled on any of the units, it is important to set the motion sensor timeout of each
unit to the same value. Otherwise, operation may not be as expected.
Lights mode is used to manually adjust any of the six lighting loads.
To enter Lights mode, raise the cover and press the Lights button. The
corresponding LED will light, and the six function buttons can now be used to adjust
lighting loads 1 through 6. Any scenes that are currently in the middle of a fade will
immediately go to their target value. The seven white front panel LEDs will go out.
In this mode, these LEDs do not reflect the feedback status of the associated scenes.
When you return to Standard mode, the LEDs will return to their standard feedback
indication.
Pressing the right side of one of the six function buttons raises the corresponding
lighting load at the ramp rate. Pressing the left side of the button lowers the
corresponding load at the ramp rate. When the button is released, the lights will stop.
The ramp rate is normally five seconds for going from full off to full on. This
can be adjusted using the iLux Designer software. Non-dim lighting loads go
immediately to full on or full off.
The bargraphs indicate current light level.
The two-digit display will indicate the current percentage level of the lighting
load being adjusted (oF, 01 to 99, on).
This display goes blank three seconds after the last adjustment.
While the front panel button is being pressed, the LED under the corresponding
bargraph will be lit solid to indicate which light level is being reflected.
The Up/Down button will act as an All Lights Master when in Lights mode, no
matter what function is programmed for it. The top button will do Master Raise
(all dimmable lighting loads), and the bottom button will do Master Lower (all
dimmable lighting loads).
The ON and OFF buttons on the CLS-C6 unit itself will operate normally while
in Lights mode as will any Scene Recall, Scene Toggle, and SceneLts_Off
commands from remote panels and Cresnet. However, during the fade, the two-
digit display will not show the fade time on the unit that is in Lights mode.
All other inputs and commands from any remote devices, motion detector, and
Cresnet Control system will be processed as usual while in Lights mode. If they
affect the lighting load (or loads) being adjusted, the manual adjustment of that
Operations Guide - DOC. 6347B