Crestron iLux CLS-C6 Operation Manual page 18

Crestron cls-c6 integrated lighting system: operations guide
Hide thumbs Also See for iLux CLS-C6:
Table of Contents

Advertisement

iLux
Lighting System
• iLux
14
Lighting System: CLS/CLSI-C6 & CLS/CLSI-C6M
Crestron CLS/CLSI-C6 & CLS/CLSI-C6M
Setup Mode Mnemonics
TWO-DIGIT
DESCRIPTION
DISPLAY
Sc
Scene Programming
Ld
Setup lighting load Load types
LE
Setup lighting load Low-End limits
HE
Setup lighting load High-End limits
bF
button Functions (i.e. recall scene, toggle scene, shades control, etc.)
ud
Set function of up/down button
oc
Setup occupancy Sensing
Ad
Run Auto-discovery
AS
Assign Shade groups
id
Set the Cresnet id of this unit
Fd
Restore Factory default
Er
Error
Press the ^ or v buttons to scroll through this list of available setup options.
Once the desired setup option appears in the display, use the various buttons on
the CLS-C6 to make adjustments, as described on the following pages.
Once any adjustment is made, Setup mode is now "locked" into that particular
option (this is indicated by lighting the period at the end of the mnemonic).
Once locked in an option, the ^ and v buttons will no longer scroll through the
options; you must exit setup before you can choose another option.
When the adjustments are complete, press Save to store the changes permanently,
and exit Setup mode, or press Cancel to exit Setup mode without saving the changes.
The unit reverts to Standard mode.
Scene Programming (Sc)
This setup option allows the user to adjust the scene parameters. This is another way
to accomplish scene changes as discussed in "Changing Scene Presets" on page 12.
This method also allows you to change the settings for scenes greater than scene 6.
Scenes can be turned off in addition to being recalled. When a scene is turned off,
only the lighting loads are turned off. If the scene contains any shades, they are not
affected. The fade time for turning the scene lights off is the same as for recalling the
scene. Therefore, no additional parameters need to be set to define the off behavior.
Select the scene to be changed using the Up/Down button. As you cycle through the
list of scenes, the lights and shades will not change, and the bargraphs will be off.
Set the lighting loads and shade positions for the scenes as discussed in "Changing
Scene Presets" on page 12. As you set the scenes, note the following:
When a lighting load reaches the HE (high end) limit, the lights will stop. The
two-digit display will continue to rise. If lights reach the LE (low end) limit, the
two-digit display will continue to go down, but lights will stay at the LE limit
until they reach Off—at which point they will turn off. If you save the scene
setting while the display is at a level below the LE limit, or above the HE limit,
the displayed value will be saved, but the light level will be limited to the
programmed limits.
If a lighting load is defined as an "unused" load type, the bargraph for that
lighting load will have all LEDs off. If you try to adjust that lighting load, the
two-digit display will show "Er".