Run Auto-Discovery (Ad)
This Setup mode is used to find which remote devices are on the network, assign
Cresnet ID's to new devices, and assign default functions to new panels and devices.
To enter this mode, first enter Setup mode and scroll to the "Ad" option (using
the ^ and v buttons). Then press the Up/Down button (either top, bottom, or
both), and hold for five seconds. The auto-discovery process will then start. (If
you release the button before five seconds are up, nothing will happen, but
"Ad." mode will be locked in.) Once "Ad." mode is locked in, the Cancel button
will flash.
During Auto discovery, the "Ad." display will flash. When Auto Discovery is
done, the two-digit display will flash between "Ad." and "##" where ## is the
number of devices discovered on the network. The Save button will also start
flashing. You can then press Save or Cancel.
The CLS-C6 keeps a list of all devices on its local network. If the auto-
discovery finds devices that match the list, it will not change anything about
those.
In addition to initially configuring the system, auto-discovery can be used to add
or replace keypads or shade controllers. If you are adding a device, all
previously assigned devices will not be changed. The new device will be added
and assigned default functionality, if desired.
To replace a device (because of defect or color choice), remove the device and
replace with another device of the same type. When you execute auto-discovery,
the new device will take on the functionality of the original device. Use the "bF"
option to change functionality, if desired.
All shade controllers of a given type will be assigned to a single shade group.
Use the "AS" option to change them.
CAUTION: If there are SSC shade controllers on the network that do not have a
functional shade connected to channel 1, shade control may not operate properly.
Therefore, any SSC shade controllers without any shades attached should be
removed from the network before running Auto-discover. Also, if any SSC shade
controllers have only one shade attached, it must be attached to channel 1.
There are a number of possible error conditions that can occur during the
discovery process (before Save is pressed). They are:
1. Corrupt data on network.
2. Two or more devices with same TSID number.
3. Invalid device type found on network. (CLS-C6 modules only support a
limited number of device types. Refer to " Appendix A: Supported
Devices" for details.
4. Too many keypads found on network. (A maximum of 16 are supported.)
5. Too many shade controllers found on network. (A maximum of 16 are
supported.)
6. (For future use.)
7. Too many slave CLSI units found on network. (A maximum of eight are
supported.)