If any of these errors occur, when the discovery process is done, the two-digit
display will flash between "Ad." "##", and "E#", where "##" is the total number
of devices discovered on the network (including invalid devices), and "E#" is
"E1" through "E7", per the seven error types listed above. If more than one error
is present, all error codes will be displayed in sequence.
In such case, the Save LED will not light (the Cancel LED will still be
flashing). The user must press Cancel, correct the error, and try again.
In the case where there were no errors during the Auto-discover process, and the
user presses Save, the CLSI will update the Network ID's for any devices which
require it.
NOTE: The case of duplicate TSIDs cannot always be accurately detected. If you
get a Corrupt Data error, or the program reports fewer devices than actually exist on
the network, this may also be a result of duplicate TSIDs. In any event,
troubleshooting for these errors is essentially the same.
Assign Shade Groups (AS)
This Setup mode is used to define which channels on each shade controller are
assigned to which shade group.
To enter this mode, first enter Setup mode and scroll to the "AS" option (using
the ^ and v buttons). Then use the Up/Down button to scroll through the shade
groups. The display will flash between "AS." and " #", where # is the shade
group to be assigned. The shade group number range is 1 – 6 plus 0 (zero). Enter
a 0 to unassign a channel. (You can also press any of the six function front panel
buttons to jump to a specific shade group.) The front panel LED corresponding
to the selected shade group will be lit.
While in AS mode, the bargraphs will indicate the status of each of the six shade
groups: if no controllers are assigned, all LEDs will be off; if SDC controller(s)
are assigned, the bottom two LEDs will be lit; if SDC-DC controller(s) are
assigned, the bottom three LEDs will be lit; if SSC controller(s) are assigned,
the top two LEDs will be lit.
When a given "AS / #" is displayed, you can press the channel 1 or channel 2 up
or down button on a shade controller to assign that channel of the shade
controller to the current group. When the button is pressed, the Setup LED on
that device will flash for one second to confirm that it has been assigned. The
bargraph for that group will also flash off for one second.
Go to a shade group and assign all channels. Then go to the next shade group
and assign those channels. Repeat for all shade groups. Note that a given shade
group can only have one type of shade controller (SDC, SDC-DC, or SSC). If a
shade controller of a given type is assigned to a group that already contains
shade controllers of the other type, the other controllers will be removed from
that group. Also, a given channel on a shade controller can only belong to a
single group. So if a shade controller that belongs to one group is assigned to a
new group, it will be removed from the first group. Therefore, if you
accidentally assign a shade controller to the wrong group, simply go to the
correct group and reassign it.
Once all shade controllers are assigned, press Save to save the assignments and
return to Standard mode, or press Cancel to discard the assignments.