Crestron CLS/CLSI-C6 & CLS/CLSI-C6M
Operations Guide - DOC. 6347B
Set Cresnet ID Of This Unit (id)
If this unit is to be connected to a Cresnet control system network, you may have to
change its Cresnet ID. (When connected to another CLS-C6 unit's local network,
you do not want to set the ID – running Auto Discovery on the master device will do
this automatically, as will the Set ID process of the iLux Designer.)
•
To do this, enter Setup mode and scroll to the "id" option, using the ^ and v
buttons.
•
The display will alternate between "id" and the current Cresnet ID. Use the
Up/Down button to adjust the ID up or down (03-FE).
Press the Save button to save the new value and return to Standard mode. Press the
Cancel button to return to Standard mode without saving – the current Cresnet ID
will be retained.
Restore Factory Defaults (Fd)
This setup mode is used to restore all settings to their factory defaults.
•
To enter this mode, first enter Setup mode and then scroll to the "Fd" option
(using the ^ and v buttons). Then press the Up/Down button (either top, bottom,
or both), and hold for five seconds.
•
This setup mode will then be locked in, and the Save LED will start flashing. (If
you release the button before five seconds are up, nothing will happen.) If you
then press Save, all configuration items will be set to their factory default
values. (If you press Cancel, the unit exits Setup mode without changes.) The
factory default configuration does not include any remote devices. If you want
to re-initialize remote devices, run Auto-discover after this function. Running
the factory default function also does not modify the Cresnet ID of the CLS-C6.
•
The Save process may take a few seconds. During this time, the Save LED will
be lit steady, and the two-digit display will show "—". When the process is
complete, the LEDs will go off.
Refer to "Appendix C: Factory Default Values" on page 45 for a list of the system
default values.
Configuring With iLux Designer
The Crestron iLux Designer application software supplied with the CLS-C6 units
configures the CLS-C6 as an independent, standalone device or as a network device
in a Crestron network control system (Cresnet system).
To configure the CLS-C6 using the iLux designer, use a direct serial connection as
described in "Programs and Firmware" on page 29. Note that connecting the serial
cable to the front panel of the CLS-C6 disconnects the control system network.
Configuring the CLS-C6 consists of setting the load schedule definition, the shade
group configuration, the scene definitions, the CLS-C6 panel configuration and
keypads configuration for each CLS-C6/C6M device. Note that only one CLS-C6
can be configured at a time. If there are multiple CLS-C6 units in a system, each one
must be individually configured.
The following are the minimum software versions required to use the iLux Designer
program.
ILux Designer version 1.02.05 or later
Crestron Toolbox version 1.01.11 or later
™