Remote Sensor Pairing Instructions – Multiple Sensors
(Wireless)
Fig. 1
Fig. 2
40
If using multiple remote temperature/humidity sensors in your
application, refer to the figures and the procedure below to change
each remote sensor's device number (Three Remote Sensors
maximum). Each Remote Sensor must have its own device
number and must also be on the same RF channel (Setting 31) as
the system they are being paired with.
1. To change the remote sensor's device number, see
the following instructions:
a. Use a pin to press the button for about half a second
and release (Fig. 1).
b. Observe the LED on the side of the remote sensor
(Fig. 2). The LED will flash once for a Device #1, twice
for a #2, three times for a #3. At any time, while in this
mode press the button once to change the device
number. Once each remote sensor has its own unique
device number simply wait for the LED to stop flashing
and the setting will be saved.
2. To change the remote sensor's RF channel, see the
following instructions:
NOTE: Check what RF Channel the System is set to using
Setting 31 to connect your Remote Sensors more easily.
a. Use a pin to press the red button at the back of the
Remote Sensor for 5 seconds until the LED blinks
rapidly then release the button.
b. The LED will flash a number of times to portray which
RF channel it is set to and repeat a total of 3 times.
c. To change the RF channel, press the button once to
increment the RF channel. There are 12 possible RF
channels. All Remote Sensors will need to be on the
same channel for the system to detect them. To save
the RF channel setting simply wait for the mode to
time out by not pressing the button.