Differential
temperature
adjustment
Temperature
deadband
Condensate
switch
Reserved
System type
defaults
Reserved
45
Setting 15
• Press "Settings" button to advance to
Setting 15
• Press the "Up" or "Down" buttons to adjust
to the desired setpoint. This setting
changes the system/compressor turn-on
temperature above setpoint. Factory default
is 1°F.
Example: Sensor reading = 55°F (13°C)
Setting 17 set to +3°F
System/compressor turns on at 58°F
(14°C)
Setting 16
• Press "Settings" button to advance to
Setting 16.
• Press the "Up" or "Down" buttons to adjust
to the desired setpoint. This setting is the
minimal allowable temperature difference
between heating and cooling setpoints.
Maximum is 5°F (3°C), minimum is 1°F
(1°C). Factory default is 2°F (1°C).
Setting 17
• Press "Settings" button to advance to
Setting 17.
• Press the "Up" or "Down" buttons to adjust
to the desired setpoint. This setting disables
or enables the Condensate switch. 0 (zero)
is disabled, 1 is enabled. Factory default is
0.
Settings 18 & 19
Reserved for additional fields.
Setting 20
System setting. DO NOT CHANGE.
Settings 21-29
Reserved for additional fields.