Defrost cut-out
temperature
Defrost check
interval
Room
temperature
offset
RH offset
44
Setting 11
• Press "Settings" button to advance to
Setting 11.
• Press the "Up" or "Down" arrow buttons to
adjust to the desired setpoint. This setting is
adjustable from 35°F to 50°F. Factory
default is 40°F.
Note: This setpoint must be 1°F/°C higher
than setting 10.
Note: If °C is selected and then switched
back to °F the default cut-out will change
to 41°F.
Setting 12
• Press "Settings" button to advance to
Setting 12.
• Press the "Up" or "Down" arrow buttons to
adjust to the desired setpoint. This setting is
adjustable from 30 min at 0 (zero), 1 hour at
1, and then in 1 hour increments up to a
maximum of 12 hours at 12.
Setting 13
• Press "Settings" button to advance to
Setting 13.
• Press the "Up" or "Down" buttons to adjust
to the desired set point. Maximum setting is
+5°F, minimum setting is -5°F. Factory
default is zero (0).
Room temperature offset changes the
actual display reading (temperature only) by
the value of this setting.
Example: Sensor reading = 55°F (13°C)
Setting 15 set to +4
Display reading = 59°F (15°C)
Setting 14
• Press "Settings" button to advance to
Setting 14
• Press the "Up" or "Down" buttons to adjust
to the desired setpoint. This setting allows
the adjustment of %RH reading by +/-10%.
Factory default is 0%RH.