Checking The Wireless Components; Commissioning; Basic Units - Siemens Albatros RVS46 Series User Manual

Zone controller
Table of Contents

Advertisement

Prerequisites
Functional check
Operating state
Diagnosis
Checking the LED
Siemens
Building Technologies
3.8.5

Checking the wireless components

To check whether the connections to the required system components are operational,
consult operating lines 130 through 135 on operating page "Wireless" (operating level

"Commissioning").

4
Commissioning
To commission the units, the following working steps must be carried out:
· Prerequisite is the correct mounting and correct electrical installation and, in the case
of wireless solutions, correctly working radio connections to all required auxiliary
units.
· Make all plant-specific settings. Special attention must be paid to operating page
"Configuration". For that purpose, the relevant operating level is to be selected as
follows:
Press OK on the room unit to switch to programming.
Press the info button for at least 3 seconds and select operating level
"Commissioning" with the setting knob. Then, press OK.
· Make the functional check as described below.
· Reset the attenuated outside temperature
(operating page "Diagnostics of consumers", operating line "Outside temp attenuated"
(operating line 8703))
To facilitate commissioning and fault tracing, the controller allows output and input tests
to be made. With these tests, the controller's inputs and outputs can be checked. To
make the tests, switch to operating page "Input / output test" and go through all
available setting lines.
The current operating state can be checked on operating page "State".
For detailed diagnostics of the plant, check operating pages "Diagnostics heat source"
and "Diagnostics consumer".

4.1 Basic units

LED off:
LED on
LED flashes
User Manual
Basic units
No power supply
Ready
Local fault
LPB
LED
31/138
CE1U2353en
2014-07-30