Siemens Albatros2 RVS46 Series User Manual
Siemens Albatros2 RVS46 Series User Manual

Siemens Albatros2 RVS46 Series User Manual

Zone controler
Hide thumbs Also See for Albatros2 RVS46 Series:

Advertisement

2
Albatros
Zone controler
User Manual OEM
Edition 1.0
Controller series A
CE1U2353en01a
22. November 2006
RVS46..
AVS75..
AVS37..
QAA75..
QAA78..
QAA55..
Building Technologies
HVAC Products

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Albatros2 RVS46 Series

  • Page 1 RVS46.. AVS75.. AVS37.. Albatros QAA75.. Zone controler QAA78.. User Manual OEM QAA55.. Edition 1.0 Controller series A Building Technologies CE1U2353en01a HVAC Products 22. November 2006...
  • Page 2 2/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products 22. November 2006...
  • Page 3: Table Of Contents

    Range of action of changeover..............22 Error....................... 23 History 1...10 ....................23 2.10 Diagnostics consumers ................. 23 Heating circuit 1, heating circuit 2, heating circuit P ........23 3/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products Table of contents 22. November 2006...
  • Page 4: Overview Of Oem Settings

    Missing ¦ Ready ¦ No reception ¦ Change batt Outside sensor Missing ¦ Ready ¦ No reception ¦ Change batt Repeater Missing ¦ Ready ¦ No reception 4/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products Overview of OEM settings 22. November 2006...
  • Page 5 24:00 hh:mm 2st phase off 24:00 00:00 24:00 hh:mm 3st phase on 24:00 00:00 24:00 hh:mm 3st phase off 24:00 00:00 24:00 hh:mm 5/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products Overview of OEM settings 22. November 2006...
  • Page 6 − − − / -30 Reduced setp increase start °C Reduced setp increase end BZ 800 °C Overtemp prot pump circuit ¦ On Mixing valve boost °C 6/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products Overview of OEM settings 22. November 2006...
  • Page 7 Mixing valve Xp °C 1136 Mixing valve Tn 1150 Floor curing function Off ¦ Functional heating ¦ Curing heating ¦ Functional/curing heating¦ Manually 7/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products Overview of OEM settings 22. November 2006...
  • Page 8 Reduced setpoint BZ 1610 °C 1614 Nominal setpoint max °C 1620 Release Time programs HCs 24h/day ¦ Time programs HCs ¦ Time program 4/DHW 8/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products Overview of OEM settings 22. November 2006...
  • Page 9 − − − / 30 3850 Collector overtemp prot °C − − − − − − / 60 3860 Evaporation heat carrier °C 9/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products Overview of OEM settings 22. November 2006...
  • Page 10 None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ DHW circulation sensor B39 5931 Sensor input BX2 None None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ DHW circulation sensor B39 10/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products Overview of OEM settings 22. November 2006...
  • Page 11 -3.0 °C 6110 Time constant building 6112 Gradient room model min/°C 6120 Frost protection plant ¦ On 6200 Saving sensors No ¦ Yes 11/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products Overview of OEM settings 22. November 2006...
  • Page 12 History 5 Error code 1 6810 History 6 Error code 6 6812 History 7 Error code 7 6814 History 8 Error code 8 12/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products Overview of OEM settings 22. November 2006...
  • Page 13 65535 Diagnostics consumers 8700 Outside temperature -50.0 50.0 °C 8703 Outside temp attenuated -50.0 50.0 °C 8704 Composite outside temperature -50.0 50.0 °C 13/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products Overview of OEM settings 22. November 2006...
  • Page 14 Relay output QX21 module 2 ¦ On 9054 Relay output QX22 module 2 ¦ On 9055 Relay output QX23 module 2 ¦ On 14/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products Overview of OEM settings 22. November 2006...
  • Page 15: The Settings In Detail

    Mixing valve Tn The integral action time is the period of time the controller’s I-part would require to produce the same change of the manipulated variable as the P-part 15/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products The settings in detail...
  • Page 16: Domestic Hot Water

    The DHW setpoint is switched between the nominal DHW setpoint and the reduced DHW setpoint according to the heating circuits’ time programs. The first switch-on point of each period is shifted forward in time by one hour. 16/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products The settings in detail 22.
  • Page 17: Pump H1/H2

    If the requested flow temperature setpoint reaches the relevant limit and the heat request increases or decreases, the flow temperature setpoint will be maintained at the maximum or minimum limit. 17/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products The settings in detail 22.
  • Page 18: Mixing Valve Control

    An adjustment of the integral action time changes the valve’s rate of response. The longer the integral action time Tn, the slower the response of the controlled system. 18/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products The settings in detail...
  • Page 19: Dhw Storage Tank

    If the DHW temperature is lower than the current setpoint minus the switching differential set here, DHW charging will be started. DHW charging will be terminated when the temperature reaches the current setpoint. 19/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products The settings in detail 22.
  • Page 20: Charging Time Limitation

    The function is always active. Automatic The function is active only if the heat source is unable to deliver heat, or is not available (fault, heat generation lock). 20/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products The settings in detail...
  • Page 21: Overtemperature Protection

    Gradient room model The room model gradient gives the period of time in minutes room heating needs to raise the temperature by 1 °C. The setting made applies to all circuits. 21/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products The settings in detail 22.
  • Page 22: Parameters

    • Segment: Changeover takes place with all controllers in the same segment. • System: Changeover takes place with all controllers in the entire system (in all segments). The controller must be located in segment 0! 22/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products The settings in detail 22.
  • Page 23: Error

    The calculation takes into account the attenuated outside temperature (operating line 8703), the room model gradient (operating line 6112) for switching to a higher setpoint, and the building’s time constant (operating line 6110) for switching to a lower setpoint. 23/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products The settings in detail 22.
  • Page 24 Saving parameter settings........22 several times / day............ 19 history reset...............23 Summer changeover ..........22 hours run device............22 switching differential DHW........19 integral action time ..........16, 18 24/26 Siemens Schweiz AG Benutzerhandbuch CE1U2354de01a HVAC Products 2 The settings in detail 22. November 2006...
  • Page 25 Hide: Ctrl+Shift+` Or put the same functionality about the following Winword menu: Menu: [Tools] - [Optionen] Option: [Highlight] In the Printfile (PDF) the change proof is not evident.’ 25/26 Siemens Schweiz AG User Manual OEM CE1U2353en01a HVAC Products 22. November 2006...
  • Page 26 Siemens Schweiz AG © 2005-2006 Siemens Building Technologies AG Siemens Switzerland Ltd Subject to alteration Building Technologies Group / HVAC Products Gubelstrasse 22 CH -6301 Zug Tel. +41 41-724 24 24 Fax +41 41-724 35 22 www.sbt.siemens.com 26/26 Siemens Schweiz AG...

Table of Contents