List Of Displays; Error Code - Siemens Albatros RVS46 Series User Manual

Zone controller
Table of Contents

Advertisement

Siemens
Building Technologies

6.22 List of displays

Priorities are assigned to pending errors. From priority 6, alarm messages are
delivered, which are used by remote supervision (OCI). In addition, the alarm relay will
be set.
6.22.1

Error code

Error code
Description of error
0
No error
10
Outside temperature sensor error
20
Boiler temperature 1 sensor error
25
Solid fuel boiler temperature (wood) sensor error
26
Common flow temperature sensor error
28
Flue gas temperature sensor error
30
Flow temperature 1 sensor error
31
Flow temperature 1 cooling, sensor error
32
Flow temperature 2 sensor error
38
Flow temperature primary controller sensor error
40
Return temperature 1 sensor error
46
Return temperature cascade sensor error
47
Common return temperature sensor error
50
DHW temperature 1 sensor error
52
DHW temperature 2 sensor error
54
DHW primary controller sensor error
57
DHW circulation temperature sensor error
60
Room temperature 1 sensor error
65
Room temperature 2 sensor error
68
Room temperature 3 sensor error
70
Buffer storage tank temperature 1 sensor error
71
Buffer storage tank temperature 2 sensor error
72
Buffer storage tank temperature 3 sensor error
73
Collector temperature 1 sensor error
74
Collector temperature 2 sensor error
81
Short-circuit LPB
82
LPB address collision
83
BSB wire short-circuit
84
BSB address collision
85
BSB radio communication fault
98
Extension module 1 fault (common fault status message)
99
Extension module 2 fault (common fault status message)
100
2 clock time masters (LPB)
102
Clock time master without backup (LPB)
105
Maintenance message
109
Boiler temperature supervision
110
Lockout by SLT
117
Upper pressure limit (crossed)
118
Critical lower pressure limit (crossed)
121
Flow temperature 1 (HC1) supervision
122
Flow temperature 2 (HC2) supervision
126
DHW charging supervision
127
Legionella temperature not reached
131
Burner fault
146
Configuration error common message
171
Alarm contact 1 (H1) active
172
Alarm contact 2 (H2) active
173
Alarm contact 3 (EX2/230VAC) active
174
Alarm contact 4 (H3) active
176
Upper pressure limit 2 (crossed)
177
Critical lower pressure limit 2 (crossed)
178
Temperature limiter heating circuit 1
179
Temperature limiter heating circuit 2
207
Error, cooling circuit
217
Sensor error common message
217
Sensor error common message
218
Pressure supervision common message
241
Flow sensor, solar sensor error
242
Return sensor, solar sensor error
User Manual
List of displays
Priority
6
9
9
6
6
6
6
6
6
6
6
6
9
9
6
6
6
6
6
6
6
6
6
6
6
3
6
3
6
6
6
3
3
5
9
9
6
6
6
6
6
6
9
3
6
6
6
6
6
6
3
3
6
6
6
6
6
6
115/138
CE1U2353en
2014-07-30

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents