Room Temp Limitation; Boost Heating - Siemens Albatros RVS46 Series User Manual

Zone controller
Table of Contents

Advertisement

Room temp limitation

Boost heating

Siemens
Building Technologies
·
"Room influence" must be set to 100 %.
·
There should be no thermostatic radiator valves in the reference room (mounting
location of the room sensor). (If such valves are present, they must be set to their
fully open position).
Line no.
HC1
HC2
HCP
760
1060
1360
The "Room temperature limitation" function enables the heating circuit pump to be
deactivated should the room temperature exceed the current room temperature
setpoint by more than the adjusted differential.
The heating circuit pump will be activated again as soon as the room temperature
returns to a level below the current room temperature setpoint.
During the time the "Room temperature limitation" function is active, no request will be
sent to the heat source.
Room temperature limitation does not work in the case of pure weather
compensation.
°C
ON
P
OFF
TRx
Actual value of room temperature
TRw
Room temperature setpoint
SDR
Room switching differential
B
Pump
t
Time
Line no.
HC1
HC2
HCP
770
1070
1370
Boost heating is used to reach the new setpoint more quickly when switching from the
Reduced setpoint to the Comfort setpoint, thus reducing the heating up time. During
boost heating, the room temperature setpoint is raised by the value set here.
A higher setting leads to shorter heating up times, a lower setting to longer heating up
times.
· Boost heating is possible with or without room sensor
User Manual
Heating circuits
Operating line
Room temp limitation
TRx
TRw+SDR
TRw
Operating line
Boost heating
t
CE1U2353en
2014-07-30
71/138