Operator Unit And Room Units Avs37 - Siemens Albatros RVS46 Series User Manual

Zone controller
Table of Contents

Advertisement

Degree of protection
Directives and
Standards
Climatic conditions
Weight
Power supply
Room temperature
measurement (only with
QAA7x... / QAA55...)
Interfaces
Degree of protection
126/138
Siemens
Building Technologies
Protection class
Protection degree of housing
Degree of pollution
Product standard
Electromagnetic compatibility
(Applications)
EU Conformity (CE)
Environmental compatibility
Storage to IEC721-3-1 class 1K3
Transport to IEC721-3-2 class 2K3
Operation to IEC721-3-3 class 3K5
Without packaging
8.3 Operator / room units AVS37.., QAA7x, QAA55
For devices without batteries:
Bus power supply
For devices with batteries:
Batteries
Type of batteries
Battery life
Measuring range:
According to EN12098:
Range 15...25 °C
range 0..15 °C or 25...50 °C
resolution
AVS37../QAA75../QAA55..
Max. cable length basic unit – peripheral
device
QAA78...
Protection class
Protection degree of housing
Degree of pollution
User Manual
Operator / room units AVS37.., QAA7x, QAA55
If correctly installed, low-voltage live parts
meet the requirements of safety class II
according to EN 60730-1
IP00 according to EN 60529
2 according to EN 60730-1
EN 60730-1
Automatic electrical controls for household
and similar use
For use in residential, commerce, light-
industrial and industrial environments
CE1T2357xx4
The product environmental declaration
CE1E2357en06 contains data on
environmentally compatible product design
and assessments (RoHS compliance,
materials composition, packaging,
environmental benefit, disposal).
temp. -20...65 °C
temp. -25...70°C
temp. 0...50 °C (noncondensing)
293 g
BSB
3 pcs
1.5 V Alkali size AA (LR06)
approx. 1.5 years
0...50 °C
within tolerance of 0.8 K
within tolerance of 1.0 K
1/10 K
BSB-W,
2-wire connection, not interchangeable
QAA75../QAA55.. = 200 m
AVS37.. =
3 m
BSB-RF
frequency band 868 MHz
If correctly installed, low-voltage live parts
meet the requirements of safety class III
according to EN 60730-1
IP20 for QAA7../ QAA55..
IP40 for AVS37.. (when mounted)
according to EN 60529
2 according to EN 60730-1
CE1U2353en
2014-07-30