Floor curing setp
manual
Floor curing setp current
Floor curing day current
Floor curing days
complete

Excess heat draw

Buffer storage tank / primary controller

With buffer storage tank
With primary controller /
system pump

Remote control

76/138
Siemens
Building Technologies
The flow temperature setpoint for the "Manual" floor-curing function can be set
separately for each heating circuit.
Shows the current flow temperature setpoint of the floor-curing process in progress
Shows the current day of the floor-curing process in progress.
Displays the number of days the requested flow temperature was met.
Fulfilled days are stored when the floor curing function is ended and remained with the
function until the next start.
Line no.
HC1
HC2
HC3P
861
1161 1461
Excess heat draw can be triggered by the following functions:
-
Inputs H1, H2, H3 or EX2
-
Storage tank recooling
-
Solid fuel boiler excess heat draw
When dissipation of excess heat is activated, it can be drawn by space heating. This
can be adjusted separately for each heating circuit.
Line no.
HC1
HC2
HCP
870
1170
1470
872
1172
1472
If there is a buffer storage tank, specify whether the heating circuit can draw heat from
it.
When using alternative heat sources, the buffer storage tank temperature is used as a
control criterion for the release of additional heat sources.
Specify whether the heating circuit receives its heat via the primary controller or with
the help of the system pump (depending on the type of plant).
Line no.
HC1
HC2
HCP
900
1200
1500
In the case of external changeover via inputs H1 / H2 / H3, the operating mode to be
used can be selected.
User Manual
Heating circuits
Operating line
Excess heat draw
Off
Heating mode
Always
Operating line
With buffer storage tank
With primary controller / system pump
Operating line
Optg mode changeover
None ¦ Protection ¦ Reduced ¦ Comfort ¦ Automatic