Setpoints

Room temperature
Frost protection
Comfort setpoint
maximum

Heating curve

Heating curve slope
Siemens
Building Technologies
Line no.
HC1
HC2
HCP
710
1010
1310
712
1012
1312
714
1014
1314
716
1016
1316
The room temperature can be shifted according to different setpoints. These setpoints
become active depending on the selected operating mode, thus producing different
temperature levels in the rooms.
The ranges of adjustable setpoints result from the interdependencies, as this is shown
in the following diagram.
0
2
4
6
TRKmax Comfort setpoint maximum
TRK
Comfort cooling setpoint
TRR
Reduced setpoint
TRF
Frost protection setpoint
In Protection mode, the room temperature is prevented from falling below a certain
level. This means that the frost protection setpoint of the room temperature will be
maintained.
The room temperature can be shifted according to different setpoints. These setpoints
become active depending on the selected operating mode, thus producing different
temperature levels in the rooms.
The ranges of adjustable setpoints result from the interdependencies, as this is shown
in the following diagram.
Line no.
HC1
HC2
HCP
720
1020
1320
721
1021
1321
726
1026
1326
The heating curve is used to generate the flow temperature setpoint, which is used to
maintain a certain flow temperature level depending on the prevailing weather
conditions. The heating curve can be adjusted with a number of settings, thus matching
heat output and room temperature to individual needs.
As the heating curve slope is raised, the flow temperature increases the quicker the
lower the outside temperature or, in other words, if the room temperature is not correct
at low outside temperatures but correct at higher outside temperatures, the heating
curve slope requires readjustment.
Increase adjustment:
Decrease adjustment:
The programmed heating curve is based on a room setpoint of 20°C. If the room
setpoint is adjusted, the heating curve automatically adapts to the new value.
User Manual
Heating circuits
Operating line
Comfort setpoint
Reduced setpoint
Frost protection setpoint
Comfort setpoint maximum
TRR
TRF
8
10
12
14
16
Operating line
Heating curve slope
Heating curve displacement
Heating curve adaption
Raises the flow temperature, especially when outside
temperatures are low.
Lowers the flow temperature, especially when outside
temperatures are low.
TRKmax
TRK
18
20
22
24
26
2358Z01
°C
67/138
CE1U2353en
2014-07-30