Siemens Albatros RVS46 Series User Manual page 98

Zone controller
Table of Contents

Advertisement

Contact type, input H...
Function value, contact H..
Voltage value 1
Function value 1
Voltage value 2
Function value 2
98/138
Siemens
Building Technologies
The linear characteristic curve is defined via two fixed points (voltage value 1 / function
value 1 and voltage value 2 / function value 2).
Room temperature 10V
The voltage signal present at input Hx is converted into a linearized room temperature
value. This, in conjunction with the indoor relative humidity, is used to calculate the
dewpoint temperature in the cooling circuit.
If there is no room unit with a room sensor (BSB) connected for heating/cooling circuit
1, the room temperature measured at Hx is also used for room heating/cooling 1
(variant with compensation and room influence).
The linear characteristic curve is defined via two fixed points (voltage value 1 / function
value 1 and voltage value 2 / function value 2).
NC
The contact is normally closed and must be opened to activate the selected function.
N/O
The contact is normally open and must be closed to activate the selected function.
The function "Min flow temp setpoint" on operating line 5950 or 6046 is activated via
contact H... The generating plant is controlled constantly at the temperature level set
here, either until contact H.. opens again or until a higher heating/cooling demand is
delivered.
Example of minimum flow setpoint:
TVw
°C
80
70
60
50
40
30
0
30
20
10
TVHw
Minimum flow temperature setpoint
TVw
Flow temperature setpoint
The linear characteristic is defined via two fixed points. The setting uses two parameter
pairs for Function value and Voltage value (F
· Example for "Heating demand 10V" and "Cooling demand 10V"
U1
Voltage value 1
F1
Function value 1
U2
Voltage value 2
F2
Function value 2
User Manual
Configuration
TVw
TVHw
TA
0
-10
°C
gem
1
/U
1 a
nd F
2
/U
2
).
CE1U2353en
2014-07-30