Siemens Albatros RVS46 Series User Manual page 99

Zone controller
Table of Contents

Advertisement

Siemens
Building Technologies
If the input signal drops below the limit value of 0.15 V, the heating demand is invalid
and therefore has no effect.
· Example of pressure measurement 10V
Druckwert [bar]
4bar
2bar
1bar
F
=0
1
0
U
=0.5V
1
U1
Voltage value 1
F1
Function value 1
U2
Voltage value 2
F2
Function value 2
· Example of relative room humidity 10V
U1
Voltage value 1
F1
Function value 1
U2
Voltage value 2
F2
Function value 2
If the measured value is below 0.15V it is regarded as invalid and an error message is
generated.
· Example of room temperature 10V
U1
Voltage value 1
F1
Function value 1
U2
Voltage value 2
F2
Function value 2
If the measured value is below 0.15V it is regarded as invalid and an error message is
generated.
User Manual
Configuration
F2=4
F2=2
F2=1
Spannung an Hx
U
=3.5V
2
99/138
CE1U2353en
2014-07-30