Types of sensor/readjustment
RVS46.543 only
RVS46.543 only
Sensor type collector
Readjustm collector
sensor
Building and room model
Frost protection for the plant
Siemens
Building Technologies
The settings for input H2 on the extension module are the same as those of the H..
inputs on the basic unit. They are described under the operating line "Function of input
H..". Siehe dazu Seite 96.
Line no.
Operating line
6097
Sensor type collector
NTC 10k
Platinum 1000
6098
Readjustm collector sensor
6100
Readjustm outside sensor
Selection of type of sensor used. The controller will use the respective temperature
characteristic.
The measured value can be corrected.
Line no.
Operating line
6110
Time constant building
When the outside temperature varies, the room temperature changes at different rates,
depending on the building's thermal storage capacity (Construction).
The above setting is used to adjust the response of the flow temperature setpoint when
the outside temperature varies.
· Example:
> 20 hours
The room temperature responds more slowly to outside temperature variations.
10 - 20 hours
This setting can be used for most types of buildings.
< 10 hours
The room temperature responds more quickly to outside temperature variations.
Line no.
Operating line
6120
Frost protection plant
The pumps are activated depending on the current outside temperature, even if there
is no heat request.
Outside temperature
(OT)
...-4 °C
-5...1.5 °C
1.5 °C...
ON
-6
-5
-4
-3
User Manual
Configuration
Pump
Continuously on
ON for 10 minutes at 6-hour intervals
Continuously off
takt
-2
-1
0
1
Graph
ON
Cycle (takt)
OFF
OFF
2
3
4
TA °C
CE1U2353en
2014-07-30
103/138