Floor Curing Function - Siemens Albatros RVS46 Series User Manual

Zone controller
Table of Contents

Advertisement

Floor curing function

Floor curing function
Siemens
Building Technologies
Line no.
HC1
HC2
HCP
850
1150
1450
851
1151
1451
1455
1456
1457
The floor curing function ensures controlled drying of the floor. It controls the flow
temperature according to a temperature profile. Drying of the floor is ensured via the
floor heating system and the mixing or pump heating circuit.
Off:
Function is deactivated.
Functional heating (Fh) :
The first part of the temperature profile is automatically completed.
Floor curing heating (Bh)
The second part of the temperature profile is traversed automatically.
Functional and floor curing heating
The entire temperature profile (first and second part) is passed automatically.
Floor curing heating and functional heating
The entire temperature profile (first and second part) is traversed automatically.
Manually
It is not a temperature profile that is completed, but the floor setpoint is controlled
manually.
· Observe the relevant standards and regulations of the floor manufacturer!
· Proper functioning is ensured only when the plant is correctly installed (hydraulic
system, electrical installation, settings)!
If not observed, the floor might get damaged!
· The function can be aborted by choosing Off.
· Maximum limitation of the flow temperature remains active.
[TVw]
55
50
45
40
35
30
25
20
0
1
5
7
1
X
Fh
1
X
Start day
Fh
Functional heating
Bh
Floor curing heating
User Manual
Heating circuits
Operating line
Floor curing function
Off
Functional heating (Fh)
Curing heating (Bh)
Functional/curing heating
Curing heating/ functional heating
Manually
Floor curing setp manually
Floor curing setp current
Floor curing day current
Floor curing days complete
5
10
Bh
Fh + Bh
15
18
[Tag
]
25
CE1U2353en
2014-07-30
75/138