Central Functions - Siemens Albatros RVS46 Series User Manual

Zone controller
Table of Contents

Advertisement

Bus power supply
Bus power supply state

Central functions

Range of action of
changeover
Summer changeover
Optg mode changeover
Manual source lock
Siemens
Building Technologies
The bus power supply enables the bus system to be powered directly by the individual
controllers (no central bus power supply). The type of bus power supply can be
selected.
· Off: No bus power supply via the controller.
· Automatically: The bus power supply (LPB) via the controller is automatically
switched on and off depending on the requirements of the LPB.
The display shows whether the controller currently supplies power to the bus:
· Off: The bus power supply via controller is currently inactive.
· On: The bus power supply via controller is currently active. At the moment, the
controller supplies some of the power required by the bus.
Line no.
Operating line
6621
Summer changeover
Locally¦ Centrally
6623
Optg mode changeover
Locally¦ Centrally
6625
DHW assignment
Local HCs
All HCs in the segment:
All HCs in system
6627
Refrigeration demand
Locally¦ Centrally
These settings are only relevant for device address 1.
The range of action of central changeover can be defined.
This concerns:
· Summer changeover (when selecting "Central" on line 6623)
· Summer changeover (with "Central" setting on operating line 6621)
Entries:
· Segment: Changeover takes place with all controllers in the same segment.
· System: Changeover takes place with all controllers in the entire system (in all
segments). The controller must be located in segment 0!
The scope of summer changeover is as follows:
· Locally:
Local action; the local heating circuit is switched based on operating lines 730, 1030
and 1330.
· Centrally:
Central action; depending on the setting made on operating line "Action changeover
functions", " either the heating circuits in the segment or those of the entire system
are switched based on operating line 730.
The range of action of operating mode changeover input via input H is as follows:
· Locally:
Local action; the local heating circuit is switched on and off.
· Centrally:
Central action; depending on the setting made on operating line "Action changeover
functions", either the heating circuits in the segment or those of the entire system are
switched based on operating line 730.
The range of the generation lock via H input is as follows:
· Locally:
Local action; the local source is locked.
· Centrally:
Central action; all sources of the cascade are locked.
User Manual
LPB system
107/138
CE1U2353en
2014-07-30