Hx Pumps; Primary Controller / System Pump - Siemens Albatros RVS46 Series User Manual

Zone controller
Table of Contents

Advertisement

Hx pumps

Excess heat draw
With buffer storage tank
With primary controller /
system pump
Refrigeration demand

Primary controller / system pump

86/138
Siemens
Building Technologies
6.9 Hx pumps
Line no.
Operating line
2010
H1 Excess heat draw
2012
H1 with storage buffer tank
2014
H1 prim contr/system pump
2015
H1 Refrig demand
2-pipe system
4-pipe system
2035
H2 Excess heat draw
2037
H2 with buffer storage tank
2039
H2 prim contr/system pump
2040
H2 Refrig demand
2-pipe system
4-pipe system
Excess heat draw can be triggered by the following functions:
-
Input H1, H2 or EX2
-
Storage tank recooling
-
Solid fuel boiler excess heat draw
When dissipation of excess heat is activated, it can be drawn by space heating. This
can be adjusted separately for each heating circuit.
If there is a buffer storage tank, this defines whether the H1/H2/H3 circuit can draw
heat from it.
When using alternative heat sources, the buffer storage tank temperature is used as a
control criterion for the release of additional heat sources.
This defines whether the H1/H2/H3 circuit receives its heat via the primary controller or
with the help of the system pump (depending on the type of plant).
2-pipe system
The cooling circuit with Hx and the heating circuits demand cooling/heating from the
same primary circuit.
4-pipe system
The cooling circuit with Hx and the heating circuits demand cooling/heating from
separate primary circuits.
6.10 Primary controller / system pump
Line no.
Operating line
2150
Primary controller / system pump
Before buffer st tank
After buffer st tank
If the plant uses a buffer storage tank, it is to be set here whether, hydraulically, the
primary controller or the system pump is installed upstream from the buffer storage
tank.
User Manual
Hx pumps
CE1U2353en
2014-07-30