136 Option
BCU1:
Step4
Stop set DI1=0
60.15 Force follower = True
19.11 Ext1/Ext2 selection =
EXT2
19.14 Ext2 control mode =
Speed
Step5
BCU1 is follower
3.13 M/F or D2D ref 1 = 200
3.14 M/F or D2D ref 2 = 15
1.1 Motor speed used = 200

Remote connectivity

Contents of this chapter

This chapter describes the installation and commissioning of remote service products. For
the drives with software version MHDRE v2.04.0.1 or higher, remote connection via NETA-
21 is possible.

Make the drive ready

Hardware connection
BCU2:
60.15 Force master = True
19.11 Ext1/Ext2 selection =
EXT1
19.12 Ext1 control mode =
Speed
BCU2 is master
Start DI1=1, give load 15%
1.1 Motor speed used = 200
1.10 Motor torque = 15%
BCU3:
60.15 Force follower = True
19.11 Ext1/Ext2 selection =
EXT2
19.14 Ext2 control mode =
Torque
BCU3 is follower
3.13 M/F or D2D ref 1 = 200
3.14 M/F or D2D ref 2 = 15
1.10 Motor torque = 15%