Motor First Run - ABB ACS580MV Commissioning Manual

200kw to 6300 kw,3.3kv to 11 kv
Hide thumbs Also See for ACS580MV:
Table of Contents

Advertisement

Set the limitation in Parameter 83.32/34 INU air pressure low/high limit.
Frame
R1
R2
Size
Low
100
100
Limit
83.32
High
800
800
Limit
83.34
Check the below signals should be similar value to ambient temperature.a.a
a. 1.31 Ambient temperature
b. 1.32 Trafo winding U1 temperature
c. 1.33 Trafo winding V1 temperature
d. 1.34 Trafo winding W1 temperature
If space heater is installed parameter 81.20 Space heater control should be activated
and test the function.

Motor first run

NOTICE Make sure you set all motor parameters and check the motor area. Nobody
and nothing should be touching the shaft or the fan when you run the motor or even
stand too close to it.
Connect the motor to drive. Let motor cooling, lubrication and protection system run if
present.
Take the drive to Local control by DriveStartup, select online mode.
Note: If can't set the speed reference by DriveStartup during the operation, try to
disconnect the USB cable in online mode and connect the cable again after the
DriveStartup announce the communication disturbing.
Press ON button on the front door, drive will be charged and fans will run.
Observe the motor behavior in the graph below. Start the motor to a low speed
reference (10% of nominal value) and check the rotation direction.
Increase the speed reference by 10% until nominal speed is reached, then decrease
the speed reference by 10% to 0.
R3
R4
R5
R6
150
100
100
200
800
800
800
800
Standard Commissioning Process 77
3.3/4.16kV
R7
R8
R6
150
100
200
800
800
800
R9
3.3/4.16kV
R9
200
150
800
800